BLD09-00887
| FIRE-Conference | 2/16/2010 | 2/16/2010 | | P | |
|
|
Don H. Phone #: ###-####
|
FIR09-00645
| FIR-Aging Inspection | 2/23/2010 | 2/23/2010 | 2/26/2010 6:21:36 PM | | DONE |
|
|
Need site inspection request for permit final.
|
FIR10-00040
| INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/24/2010 4:20:15 PM | P | PASS |
|
|
Scope of fire alarm work per permit documents passed after hours site inspection.
|
FIR09-00516
| INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 4:43:04 PM | A | FAIL |
|
|
Several items noted during field inspection include; incorrect cd ratings at appliances in lobby 214 and hallway 213, sd at hallway 131 too close to an HVAC grill, notification device at hallway 129 overspaced off the end of the corridor, noted 14ga wire at notification circuts where 16ga is shown per plan, missing the smoke detector at lobby 102, strobe location at RR 107 has been moved, missing horn at B-2-13 EOL, plans show a strobe only at vestibule 201, hi/lo pressure switch not used per matrix, damper at ID S15 is not functional, sample tube at the duct detector does not appear to be supported or extend through the ductwork at the other side- see plan note #4, offsite monitoring reports the incorrect building address to dispatch. NOTE: Most issues repaired or adjusted while on site, the balance of system testing passed, remainder of outstanding items to be re-tested tomorrow as discussed. Request a copy of the list of signals sent today including correct address at next site visit. Added relay for the delayed egress hardware tested okay.
|
FIR03-00061
| INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 4:19:03 PM | P | PASS |
|
|
Okay to final permit per project related BLD activity notes and site inspection notes for work completed.
|
FIR09-00419
| INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 4:15:47 PM | P | PASS |
|
|
UG fire supply line permit work okay for final status per activity notes and overhead system testing for project related FIR's.
|
BLD10-00162
| FIRE-Final Inspection | 2/22/2010 | 2/23/2010 | 2/23/2010 4:12:10 PM | P | PASS |
|
|
Items on correction notice completed satisfactory with the exception of panic hardware at the north exit in progress of installation at the time of inspection, one EM light repaired while on site. Single action hardware to be finished for prior to structrual final inspection as agreed.
|
FIR09-00708
| INSP-Sprinkler Rough-in | 2/23/2010 | 2/23/2010 | 2/23/2010 4:07:44 PM | P | PART |
|
|
Begin 24 hour air test at the 4" dry valve at 3:30PM @48 psig.
|
FIR09-00494
| INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 4:02:59 PM | P | NR |
|
|
Partial inspection- Noted three obstructed pendent heads- one each at a storage room, isolation room, and detox room, need to complete forward flow test, missing the cover at the flow switch, two curtains at the womens sleep room are not installed, project related fire alarm permit is not yet finaled- however sprinkler riser monitoring tested okay.
|
BLD08-02569
| BLD-Aging Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 3:55:10 PM | A | FAIL |
|
|
Project related fire sprinkler permit needs finaled, BLD permit is described as a vanilla shell however it appears the tenant has taken occupancy of the area within the scope of work.
|
FIR08-00860
| INSP-Sprinkler Rough-in | 2/23/2010 | 2/23/2010 | 2/23/2010 3:50:40 PM | A | NH |
|
|
Missing plans on site for annotations regarding previous inspection comments.
|
FIR10-00041
| INSP-Sprinkler Rough-in/Hydro | 2/23/2010 | 2/23/2010 | 2/23/2010 3:47:32 PM | A | PART |
|
|
Final pending ceiling tile and escutcheons.
|
BLD10-00249
| FIRE-Final Inspection | 2/22/2010 | 2/23/2010 | 2/23/2010 3:46:23 PM | A | FAIL |
|
|
Need to post signage at the main entry/exit door, missing one fire extinguisher to be posted as discussed with a current certification tag- see general requirements sheet with issued permit documents for details.
|
FIR09-00516
| INSP-Sprinkler Rough-in/Hydro | 2/22/2010 | 2/23/2010 | 2/23/2010 8:26:23 AM | P | CANC |
|
|
Dave Dilley is doing the inspection. Inspection requested from web by: Mike Brown Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|