ELE12-00288
| Electrical Rough-In | 2/22/2012 | 2/23/2012 | 2/24/2012 3:12:55 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by mark hood
|
ELE12-00365
| Electrical Rough-In | 2/22/2012 | 2/23/2012 | 2/24/2012 11:47:41 AM | A | CANC |
|
|
Building #24 Rough-in exact same material as all others Phone #: ###-#### >> Inspection requested via web by Tyler Bowen
|
ELE12-00077
| Electrical Rough-In | 2/21/2012 | 2/23/2012 | 2/23/2012 3:40:33 PM | P | FAIL |
|
|
Dave. Ceiling cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ID cable support wires, shall not use fixture support wires for required support wires 300.11, note all low voltage cables shall be support off of grid , and shall not use ceiling support wires to support them if ? call Jack
|
ELE12-00331
| Rough-In Permanent Service | 2/23/2012 | 2/23/2012 | 2/23/2012 3:36:39 PM | P | PASS |
|
|
Please contact Cody ###-#### with any questions. Phone #: ###-#### >> Inspection requested via web by Tracy Robertson p/s u/g new ok
|
ELE12-00349
| Rough-In Permanent Service | 2/22/2012 | 2/23/2012 | 2/23/2012 3:36:13 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson called contractor needs to grd, or bond water pipe 250.52(A)(1) or 104 (A)(1) also connector for GEC
|
ELE12-00142
| Rough-In Permanent Service | 2/22/2012 | 2/23/2012 | 2/23/2012 2:54:13 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Joe Thomas calc p/s called r/i ok, p/s u/g new ok
|
ELE12-00372
| Rough-In Permanent Service | 2/23/2012 | 2/23/2012 | 2/23/2012 10:37:46 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI called corr. all outside boxes shall be flush with siding at time of inspection, shall install all outside recess cans
|
ELE12-00350
| Temporary Service | 2/22/2012 | 2/23/2012 | 2/23/2012 9:14:19 AM | A | PASS |
|
|
Temp power. re inspect. CJ is contact. Thanks Phone #: ###-#### >> Inspection requested via web by Chris Chesnut t/s u/g new ok
|
ELE12-00192
| Final | 2/21/2012 | 2/23/2012 | 2/23/2012 8:29:53 AM | A | NR |
|
|
Please call Lynn Proctor at ###-#### with approximate inspection time. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor correction posted for required sign branch circuit and show window recepts 600.5 and 210.62 note job checked out for final and r/i for ceiling see added r/i
|
ELE12-00192
| Electrical Rough-In | 2/23/2012 | 2/23/2012 | 2/23/2012 8:29:44 AM | P | PASS |
|
|
Please call Lynn Proctor at ###-#### with approximate inspection time. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor ceiling ok
|