Inspections for the day of: Thursday, February 23, 2012.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00680 INSP-Sprinkler Rough-in2/23/20122/23/20122/24/2012 6:45:12 AMPPART
UG fire supply line from the contractor point of connection to the IBR is approved for bury.
FIR09-00375 INSP-Final Inspection2/21/20122/23/20122/24/2012 6:42:51 AMPPASS
Fire alarm permit finaled. Inspection passed.
BLD11-02990 FIRE-Final Inspection2/23/20122/23/20122/24/2012 6:41:55 AMPPASS
FIR11-00550 INSP-Alarm Testing2/23/20122/23/20122/24/2012 6:41:37 AMAPART
FIR11-00448 INSP-Sprinkler Rough-in/Hydro2/22/20122/23/20122/23/2012 1:31:28 PMAFAIL
System 10 inspection failed due to multiple deficiencies including; mechanical room 44- overspaced coverage at the west wall, five uprights below max. distance from the deck, missing seismic brace at 4" main, 3" main has been installed in place of 2 1/2" per the approved plan, 4" main installed on the opposite side of the beam, 6" feed main has been relocated, four 45 deg. ells have been added to the 4" main. Missing retainer at NW stair 60, four added 45 ells at S/W stair main. Mechanical access area- 4 upright heads exceed min. separation distances, added 90's at branchline, missing retainers, overspaced upright adjacent to division wall. Mechanical mezzanine 43- blocked heads at new beams, 10 added 90's at one 2" branchline, several sprig-ups are out of axis, noted approx. 15 added heads under various obstructions which are not included in the design. Access unavailable at one portion of the mechanical service area. Due to project schedule and a majority of plant process equipment already installed, some aspects of the system are not accessible for satisfactory inspection.