FIR11-00563
| INSP-Sprinkler Rough-in/Hydro | 2/23/2012 | 2/23/2012 | 2/23/2012 3:14:23 PM | P | PART |
|
|
Todays inspection was for several rooms on the fourth floor. Piping installed does not match the city approved plans in the three rooms around the exterior balcony. Piping can not be covered in this area.
|
BLD11-01251
| FIRE-Final Inspection | 2/23/2012 | 2/23/2012 | 2/23/2012 3:01:07 PM | P | PASS |
|
|
life safety passed
|
FIR12-00084
| INSP-Alarm Testing | 2/22/2012 | 2/23/2012 | 2/23/2012 2:02:36 PM | A | PASS |
|
|
Permit finaled
|
FIR10-00039
| FIR-Aging Inspection | 2/23/2012 | 2/23/2012 | 2/23/2012 10:55:51 AM | | NR |
|
|
I spoke to Mary about this permit and FIR10-00036 which are at the same address.
|
BLD12-00303
| FIRE-Final Inspection | 2/22/2012 | 2/23/2012 | 2/23/2012 9:44:30 AM | A | FAIL |
|
|
There appears to be no off site monitoring of the existing fire sprinkler system. Sentry Security Systems was on site and said that they are going to take over the monitoring account. Also two exit signs as shown on the plans have not been installed. I went over the exit sign requirements with Terry.
|
BLD11-01251
| FIRE-Final Inspection | 2/22/2012 | 2/23/2012 | 2/23/2012 8:34:15 AM | A | FAIL |
|
|
Provide the missing door hardware and the missing exit sign. Rescheduled for this afternoon.
|