Inspections for the day of: Monday, February 23, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02791 ELE-Aging Inspection2/23/20152/23/20152/23/2015 2:12:58 PM DONE
construction still incomplete, posted notice on side window with other inspection stickers. 2-23-15 2:15 PM
ELE13-00162 ELE-Aging Inspection2/23/20152/23/20152/23/2015 1:56:09 PM DONE
Corrections made, Final OK
ELE13-00162 Final2/23/20152/23/20152/23/2015 1:56:00 PMPPASS
corrections made, final OK
ELE14-00440 Electrical Rough-In2/23/20152/23/20152/23/2015 1:46:30 PMPPASS
Dan Phone #: ###-####
OK to cover one wire in insulated wall, services exterior wall mounted light on SW wall between the two man doors about 12 feet up.
ELE15-00448 Rough-In Permanent Service2/20/20152/23/20152/23/2015 10:15:53 AMAFAIL
Thanks Phone #: ###-#### Inspection requested via web by Darryn Coburn
called
300.4 NM cable through bored holes shall have protection where edge of bored hole is less than 1 1/4 inch from edge of framing member
320.23 Guard stripps required within six foot of attic access
300.13 B Multi wire branch circuit grounded conductor can not depend on device
406.5 Srews used for attaching receptacles to a box shall be a machine type screw having 32 threads per inch
ELE15-00434 Electrical Rough-In2/20/20152/23/20152/23/2015 9:25:23 AMAPASS
rough in for a possible solar installation in the future.
Phone #: ###-#### Inspection requested via web by Ryan King
Prewire for future solar, j-box in attic near access. ground clamped to EGC for home with irreversible clamp. Disconnect next to meter.
ELE15-00407 Electrical Rough-In2/19/20152/23/20152/23/2015 8:43:33 AMAFAIL
Suite 208 known as TMN Events. General Contractor is Owyhee Enterprises. Phone #: ###-#### Inspection requested via web by Paula Gratiot
left message.
300.4(A) Cables and Raceways Through Wood Members.
(1) Bored Holes. In both exposed and concealed locations,
where a cable- or raceway-type wiring method is installed
through bored holes in joists, rafters, or wood members,
holes shall be bored so that the edge of the hole is not less
than 32 mm (11/4 in.) from the nearest edge of the wood
member. Where this distance cannot be maintained, the
cable or raceway shall be protected from penetration by
screws or nails by a steel plate(s) or bushing(s), at least
1.6 mm (1/16 in.) thick, and of appropriate length and width
installed to cover the area of the wiring.