ELE07-02791
| ELE-Aging Inspection | 2/23/2015 | 2/23/2015 | 2/23/2015 2:12:58 PM | | DONE |
|
|
construction still incomplete, posted notice on side window with other inspection stickers. 2-23-15 2:15 PM
|
ELE13-00162
| ELE-Aging Inspection | 2/23/2015 | 2/23/2015 | 2/23/2015 1:56:09 PM | | DONE |
|
|
Corrections made, Final OK
|
ELE13-00162
| Final | 2/23/2015 | 2/23/2015 | 2/23/2015 1:56:00 PM | P | PASS |
|
|
corrections made, final OK
|
ELE14-00440
| Electrical Rough-In | 2/23/2015 | 2/23/2015 | 2/23/2015 1:46:30 PM | P | PASS |
|
|
Dan Phone #: ###-#### OK to cover one wire in insulated wall, services exterior wall mounted light on SW wall between the two man doors about 12 feet up.
|
ELE15-00448
| Rough-In Permanent Service | 2/20/2015 | 2/23/2015 | 2/23/2015 10:15:53 AM | A | FAIL |
|
|
Thanks Phone #: ###-#### Inspection requested via web by Darryn Coburn called 300.4 NM cable through bored holes shall have protection where edge of bored hole is less than 1 1/4 inch from edge of framing member 320.23 Guard stripps required within six foot of attic access 300.13 B Multi wire branch circuit grounded conductor can not depend on device 406.5 Srews used for attaching receptacles to a box shall be a machine type screw having 32 threads per inch
|
ELE15-00434
| Electrical Rough-In | 2/20/2015 | 2/23/2015 | 2/23/2015 9:25:23 AM | A | PASS |
|
|
rough in for a possible solar installation in the future. Phone #: ###-#### Inspection requested via web by Ryan King Prewire for future solar, j-box in attic near access. ground clamped to EGC for home with irreversible clamp. Disconnect next to meter.
|
ELE15-00407
| Electrical Rough-In | 2/19/2015 | 2/23/2015 | 2/23/2015 8:43:33 AM | A | FAIL |
|
|
Suite 208 known as TMN Events. General Contractor is Owyhee Enterprises. Phone #: ###-#### Inspection requested via web by Paula Gratiot left message. 300.4(A) Cables and Raceways Through Wood Members. (1) Bored Holes. In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 32 mm (11/4 in.) from the nearest edge of the wood member. Where this distance cannot be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate(s) or bushing(s), at least 1.6 mm (1/16 in.) thick, and of appropriate length and width installed to cover the area of the wiring.
|