Inspections for the day of: Tuesday, February 24, 2004.
Number of inspections: 34
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02287 FIRE-Conference2/23/20042/24/20042/24/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 2/23/2004 at 11:04:03 AM. Contact: ###-####. met with GC about fire extinguisher placement - will two additional at stair doors and the others as shown on plans 2/24/2004 8:52:35 AM
BLD03-02953 FIRE-Final Inspection2/23/20042/24/20042/24/2004 12:00:00 AMAPASS
Dennis; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
FIR03-00538 INSP-Supply line flush2/23/20042/24/20042/24/2004 12:00:00 AMAPASS
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see UG permit; flush okay - still needs hydro 2/24/2004 8:16:40 AM
FIR03-00616 INSP-Sprinkler Rough-in/Hydro2/23/20042/24/20042/24/2004 12:00:00 AMAPART
mike; Phone #: ###-#### Internet Inspection Request from: Annette Moore UG flush only for the relocated building sprinkler system - okay; attempted to forward flow the BFP through the 2 inch drain and the pitot reading was 10 psi - needed 12 psi to obtain the required flow 2/24/2004 10:06:41 AM
FIR03-00788 INSP-Final Inspection2/23/20042/24/20042/24/2004 12:00:00 AMACANC
CLIFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs--cancel per cilff
FIR03-00315 INSP-Final Inspection2/23/20042/24/20042/24/2004 12:00:00 AMANR
CLIFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs rescheduled for 34/1/04 2/24/2004 8:41:10 AM
FIR04-00065 INSP-Sprinkler Rough-in/Hydro2/23/20042/24/20042/24/2004 12:00:00 AMAPASS
jim ; Phone #: ###-#### Internet Inspection Request from: Annette Moore R/I okay - per plans 2/24/2004 10:07:42 AM
FIR03-00495 INSP-Supply line flush2/24/20042/24/20042/24/2004 12:00:00 AMAPASS
UG flush okay; still needs hydro 2/24/2004 8:17:04 AM
FIR03-00538 INSP-Sprinkler Rough-in2/24/20042/24/20042/24/2004 12:00:00 AMPFAIL
heads not installed in two areas; painted heads and heads with tape; SE area, elevator pit, electrical room not completed; no access to SW area; see plans for the above 2/24/2004 2:15:23 PM
FIR03-00153 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/24/2004 at 8:20:12 AM. Contact: ###-####.
FIR03-00154 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/24/2004 at 8:20:35 AM. Contact: ###-####.
FIR03-00155 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/24/2004 at 8:21:01 AM. Contact: ###-####.
FIR03-00156 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/24/2004 at 8:21:49 AM. Contact: ###-####.
FIR03-00157 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/24/2004 at 8:22:15 AM. Contact: ###-####.
FIR03-00158 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/24/2004 at 8:22:52 AM. Contact: ###-####.
FIR03-00159 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 2/24/2004 at 8:23:26 AM. Contact: ###-####. The access control elevator lobby doors will need to be tested to verify they release on fire alarm; they will not be active until after the acceptance by the inspector; the remote annunciator at the ramp is not listed for out in the elements 2/24/2004 4:29:07 PM
FIR03-00067 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00088 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPFAIL
We would like a final this PM. Please
call prior to arrival; Phone #: ###-#### Internet Inspection Request from: Trent Bice west courtyard corridor is not completed - need armovers for two drop in soffit 2/24/2004 4:22:35 PM
FIR03-00088 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPFAIL
We would like a final this PM. Please
call prior to arrival; Phone #: ###-#### Internet Inspection Request from: Trent Bice west courtyard corridor is not completed - need armovers for two drop in soffit 2/24/2004 4:22:35 PM
FIR03-00115 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00115 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00135 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00135 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00136 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00136 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00137 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00137 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00138 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00138 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00139 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00139 INSP-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPASS
We would like a final this PM. Please call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
BLD03-02875 FIRE-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPPART
mike ; Phone #: ###-#### Internet Inspection Request from: Annette Moore per Dave Miller a temp occupancy has been approved pending installation of the smoke/fire damper and testing of the fire alarm system 2/24/2004 12:41:58 PM
BLD04-00277 FIRE-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPNH
###-#### Jenn -- having BLD final this afternoon as well. Left message and will reschedule for 2/25 AM 2/24/2004 4:08:53 PM
BLD03-01845 FIRE-Conference2/17/20042/24/20042/24/2004 12:00:00 AMPPASS
follow up for 5 day notice talked to manager of BD foods and he has Sentry Security involved to update the fire alarm panel and Phil Omas will get drawings and submit plans for the permit 2/24/2004 12:39:57 PM