Inspections for the day of: Tuesday, February 24, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00794 INSP-Sprinkler Rough-in/Hydro2/23/20042/24/20042/24/2004 12:00:00 AMAPART
24 hour air test is ok and forward flush of the backflow preventor is ok 2/24/2004 9:09:38 AM
FIR04-00045 INSP-Sprinkler Rough-in/Hydro2/23/20042/24/20042/24/2004 12:00:00 AMAPASS
sprinkler piping is ok to cover 2/24/2004 8:45:05 AM
BLD03-02352 FIRE-Final Inspection2/23/20042/24/20042/24/2004 12:00:00 AMAFAIL
Provide approved door hardware per plans. Remove the thumbturn from the main exit and the closet. Provide door to remain unlocked stickers at the doors 2/23/2004 3:34:22 PM
BLD03-00602 FIRE-Final Inspection2/23/20042/24/20042/24/2004 12:00:00 AMAFAIL
Inspection was not a final but for inspection on the remaining fire dampers. Fire dampers are ok to cover 2/24/2004 2:48:02 PM
MIS04-00047 FIR-Final2/24/20042/24/20042/24/2004 12:00:00 AMPFAIL
Provide a code compliant fire alarm system per review note #2. This will require a new permit to be issued since the original was expired. Provide suite number. Repair the exit sign at the main exit. Sprinkler pendant in the women's restroom is closer than 1' from a supply register. Mount fire extinguishers at 48" above finish floor. Cover electrical junction boxes in upstairs room. Remove dead bolts on exit doors in warehouse 2/24/2004 2:26:03 PM
BLD04-00099 FIRE-Final Inspection2/24/20042/24/20042/24/2004 12:00:00 AMPFAIL
sprinkler pendant is overspaced off of the breakroom wall (9'-4") 2/24/2004 2:16:08 PM
FIR03-00713 INSP-Sprinkler Rough-in/Hydro2/23/20042/24/20042/24/2004 12:00:00 AMPFAIL
connect flow switch to the alarm system per review note #16. Flush underground per note #12. Lock valves of backflow preventor in open position. Remove ball valve that is in place before the backflow preventor. Provide data sheet for the backflow preventor since what is installed in not what was submitted. Provide correct orfice on the inspectors test. 2/24/2004 3:50:36 PM
FIR04-00037 INSP-Final Inspection2/23/20042/24/20042/24/2004 12:00:00 AMPPART
Areas 1-4, 1-5, 1-6 and 1-8 are complete 2/24/2004 3:16:05 PM