FIR03-00794
| INSP-Sprinkler Rough-in/Hydro | 2/23/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | A | PART |
|
|
24 hour air test is ok and forward flush of the backflow preventor is ok 2/24/2004 9:09:38 AM
|
FIR04-00045
| INSP-Sprinkler Rough-in/Hydro | 2/23/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | A | PASS |
|
|
sprinkler piping is ok to cover 2/24/2004 8:45:05 AM
|
BLD03-02352
| FIRE-Final Inspection | 2/23/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | A | FAIL |
|
|
Provide approved door hardware per plans. Remove the thumbturn from the main exit and the closet. Provide door to remain unlocked stickers at the doors 2/23/2004 3:34:22 PM
|
BLD03-00602
| FIRE-Final Inspection | 2/23/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | A | FAIL |
|
|
Inspection was not a final but for inspection on the remaining fire dampers. Fire dampers are ok to cover 2/24/2004 2:48:02 PM
|
MIS04-00047
| FIR-Final | 2/24/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | P | FAIL |
|
|
Provide a code compliant fire alarm system per review note #2. This will require a new permit to be issued since the original was expired. Provide suite number. Repair the exit sign at the main exit. Sprinkler pendant in the women's restroom is closer than 1' from a supply register. Mount fire extinguishers at 48" above finish floor. Cover electrical junction boxes in upstairs room. Remove dead bolts on exit doors in warehouse 2/24/2004 2:26:03 PM
|
BLD04-00099
| FIRE-Final Inspection | 2/24/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | P | FAIL |
|
|
sprinkler pendant is overspaced off of the breakroom wall (9'-4") 2/24/2004 2:16:08 PM
|
FIR03-00713
| INSP-Sprinkler Rough-in/Hydro | 2/23/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | P | FAIL |
|
|
connect flow switch to the alarm system per review note #16. Flush underground per note #12. Lock valves of backflow preventor in open position. Remove ball valve that is in place before the backflow preventor. Provide data sheet for the backflow preventor since what is installed in not what was submitted. Provide correct orfice on the inspectors test. 2/24/2004 3:50:36 PM
|
FIR04-00037
| INSP-Final Inspection | 2/23/2004 | 2/24/2004 | 2/24/2004 12:00:00 AM | P | PART |
|
|
Areas 1-4, 1-5, 1-6 and 1-8 are complete 2/24/2004 3:16:05 PM
|