ELE05-00141
| Rough-In Permanent Service | 2/23/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/23/2005 at 12:49:05 PM. Contact: ###-####. r/i ok
p/s o/h new ok 2/24/2005 10:00:38 AM
|
ELE05-00573
| Temporary Service | 2/23/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/23/2005 at 1:21:57 PM. Contact: ###-####. t/s o/h new ok 2/24/2005 7:59:22 AM
|
ELE05-00545
| Permanent Service | 2/23/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | FAIL |
|
|
charles; Phone #: ###-#### Internet Inspection Request from: Barbara Moore not one thing right with the whole job owner had other people doing work, panel in warm wall, no grd needs to update mast to 2" had conference mentioned too owner he really needs electrical contractor C O W 2/24/2005 10:19:07 AM
|
ELE05-00406
| Final | 2/23/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | PASS |
|
|
###-#### - JESS ok card signed 2/24/2005 8:42:52 AM
|
ELE05-00590
| Electrical Rough-In | 2/23/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | FAIL |
|
|
We:1)extended a spare 120 volt circuit that was in the crawl space up to a new receptacle for his microwave. 2)wired a new 20 amp 220 volt recept in garage for heater to plug into.We are totally done now.Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
cor. 400.8 shall not use cord as fixed wiring, garage heater, 210.8 needs gfci for MB wall recept called 2/24/2005 9:14:59 AM
|
ELE05-00567
| Electrical Rough-In | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/24/2005 at 7:29:45 AM. Contact: ###-####. ok 2/24/2005 11:34:08 AM
|
ELE05-00406
| Electrical Rough-In | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | A | PASS |
|
|
ceiling ok for cover
|
ELE05-00599
| Final | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | PASS |
|
|
###-#### - darrell u/g r/i ok final ok
2/24/2005 2:02:15 PM
|
ELE05-00059
| Final | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | PART |
|
|
partial final for front office cubicles, please contact Steve, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters t/o for front section ok 2/24/2005 4:20:10 PM
|
ELE04-01713
| Final | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | PART |
|
|
Residence Inn - Gatehouse & Poolhouse only.Thanks; Phone #: ###-#### Internet Inspection Request from: Barry Kendall needs gfci for kit recepts, clear space 110.26 for panel in pool equip rm, 250.122 needs #8 equip grd pole lights 2/24/2005 4:22:39 PM
|
ELE05-00575
| Final | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | NR |
|
|
Call Joe for entrance.; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt cor met wtih contractor, needs clearence for sub pane, use manufactures listed breakers see added p/s 2/24/2005 3:15:49 PM
|
ELE05-00260
| Final | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | PASS |
|
|
please call after inspection with results//dallas; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 2/24/2005 12:20:19 PM
|
ELE04-03600
| Final | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs survey posted protect romex in island cabinet, final ok 2/24/2005 1:35:57 PM
|
ELE05-00575
| Permanent Service | 2/24/2005 | 2/24/2005 | 2/24/2005 12:00:00 AM | P | PASS |
|
|
p/s o/h rec. ok
|