ELE05-00855
| Final | 2/24/2006 | 2/24/2006 | 2/24/2006 4:34:59 PM | P | FAIL |
|
|
CONTACT: GREG PACK; Phone #: ###-#### Internet Inspection Request from: Deb McCoy met contr, left corr notice, 408.4 circuit directory shall be clear, concise evident for each circuit, 358.12(5) emt shall not be used for fixture support, 358.26 there shall not be over 360 degrees bend in emt between pull points,358.30(A) emt shall be securely fastened within 3' of conduit body, 110.12(A) unused openings shall be closed in boxes, 314.25 boxes shall have covers installed, 410.14(B) electric discharge fixtures surface mounted over concealed boxes, unless designed to be supported by box, shall be provided with openings to provide wiring access, 300.3(C)(1) all circuit conductors shall have insulation rating equal to maximum circuit voltage applied to any conductor in enclosure, 400.8(2) flexible cord shall not be run thru walls, 110.2 equipment shall be acceptable only if approved (parking attendant stations), 427.11 pipeline heating equipment shall be installed to avoid physical damage, NOTE: access to 4th floor via stairs shall be prohibited
|
ELE05-04257
| Final | 2/24/2006 | 2/24/2006 | 2/24/2006 3:47:36 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called contr, left corr notice, BCC shall see u/g before cover for post light, rest of house ok
|
ELE06-00150
| Final | 2/24/2006 | 2/24/2006 | 2/24/2006 3:05:21 PM | P | PART |
|
|
jeremiah; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa still installing equipment
|
ELE06-00639
| Temporary Service | 2/24/2006 | 2/24/2006 | 2/24/2006 12:55:22 PM | P | PASS |
|
|
Sean; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
|
ELE06-00648
| Temporary Service | 2/24/2006 | 2/24/2006 | 2/24/2006 12:53:46 PM | P | PASS |
|
|
Internet Inspection Request from: Cevyn Recla t/s u/g n ok
|
ELE06-00647
| Temporary Service | 2/24/2006 | 2/24/2006 | 2/24/2006 12:52:43 PM | P | PASS |
|
|
Internet Inspection Request from: Cevyn Recla t/s u/g n ok
|
ELE06-00629
| Final | 2/23/2006 | 2/24/2006 | 2/24/2006 11:58:42 AM | P | PASS |
|
|
We upgraded the service and panel to 200 amps. We will call you when we are done so you can inspect at your earliest convenience and call Idaho Power so they will re-energize this service.THANKS!!!!!!!Dan(#6020166mcmillan) We also wired a new 120 volt receptacle in the laundry room.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell p/s u/g reconnect ok
|
ELE06-00594
| Rough-In Permanent Service | 2/23/2006 | 2/24/2006 | 2/24/2006 9:52:50 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ric ok, p/s u/g n ok
|
ELE06-00079
| Final | 2/22/2006 | 2/24/2006 | 2/24/2006 9:29:45 AM | A | PASS |
|
|
Inspection for spa and outlet for welder and aircompressor in garage.; Phone #: ###-#### Internet Inspection Request from: Adam Staigle ok to final
|
ELE06-00309
| Electrical Rough-In | 2/23/2006 | 2/24/2006 | 2/24/2006 9:03:00 AM | A | PASS |
|
|
please inspect the barn again. thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas corr made, ric ok, called contr to provide ko seal in bottom of panel
|
ELE05-04467
| Permanent Service | 2/24/2006 | 2/24/2006 | 2/24/2006 8:43:02 AM | P | PASS |
|
|
re-inspect for perm service. Bob, please inspect asap as per our conversation this am. Please call me as soon as you have an idea when you can inspect so I can call IDPCO to let them know when to re-connect. Thank you.; Phone #: ###-#### Internet Inspection Request from: todd hall p/s reconnect o/h ok
|
ELE05-04588
| Final | 2/23/2006 | 2/24/2006 | 2/24/2006 8:13:15 AM | A | PART |
|
|
Clint; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong looked at trim, still installing equip
|