Inspections for the day of: Friday, February 24, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00855 Final2/24/20062/24/20062/24/2006 4:34:59 PMPFAIL
CONTACT: GREG PACK; Phone #: ###-#### Internet Inspection Request from: Deb McCoy met contr, left corr notice, 408.4 circuit directory shall be clear, concise evident for each circuit, 358.12(5) emt shall not be used for fixture support, 358.26 there shall not be over 360 degrees bend in emt between pull points,358.30(A) emt shall be securely fastened within 3' of conduit body, 110.12(A) unused openings shall be closed in boxes, 314.25 boxes shall have covers installed, 410.14(B) electric discharge fixtures surface mounted over concealed boxes, unless designed to be supported by box, shall be provided with openings to provide wiring access, 300.3(C)(1) all circuit conductors shall have insulation rating equal to maximum circuit voltage applied to any conductor in enclosure, 400.8(2) flexible cord shall not be run thru walls, 110.2 equipment shall be acceptable only if approved (parking attendant stations), 427.11 pipeline heating equipment shall be installed to avoid physical damage, NOTE: access to 4th floor via stairs shall be prohibited
ELE05-04257 Final2/24/20062/24/20062/24/2006 3:47:36 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called contr, left corr notice, BCC shall see u/g before cover for post light, rest of house ok
ELE06-00150 Final2/24/20062/24/20062/24/2006 3:05:21 PMPPART
jeremiah; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa still installing equipment
ELE06-00639 Temporary Service2/24/20062/24/20062/24/2006 12:55:22 PMPPASS
Sean; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
ELE06-00648 Temporary Service2/24/20062/24/20062/24/2006 12:53:46 PMPPASS
Internet Inspection Request from: Cevyn Recla t/s u/g n ok
ELE06-00647 Temporary Service2/24/20062/24/20062/24/2006 12:52:43 PMPPASS
Internet Inspection Request from: Cevyn Recla t/s u/g n ok
ELE06-00629 Final2/23/20062/24/20062/24/2006 11:58:42 AMPPASS
We upgraded the service and panel to 200 amps. We will call you when we are done so you can inspect at your earliest convenience and call Idaho Power so they will re-energize this service.THANKS!!!!!!!Dan(#6020166mcmillan) We also wired a new 120 volt receptacle in the laundry room.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell p/s u/g reconnect ok
ELE06-00594 Rough-In Permanent Service2/23/20062/24/20062/24/2006 9:52:50 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ric ok, p/s u/g n ok
ELE06-00079 Final2/22/20062/24/20062/24/2006 9:29:45 AMAPASS
Inspection for spa and outlet for welder and aircompressor in garage.; Phone #: ###-#### Internet Inspection Request from: Adam Staigle ok to final
ELE06-00309 Electrical Rough-In2/23/20062/24/20062/24/2006 9:03:00 AMAPASS
please inspect the barn again. thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas corr made, ric ok, called contr to provide ko seal in bottom of panel
ELE05-04467 Permanent Service2/24/20062/24/20062/24/2006 8:43:02 AMPPASS
re-inspect for perm service. Bob, please inspect asap as per our conversation this am. Please call me as soon as you have an idea when you can inspect so I can call IDPCO to let them know when to re-connect. Thank you.; Phone #: ###-#### Internet Inspection Request from: todd hall p/s reconnect o/h ok
ELE05-04588 Final2/23/20062/24/20062/24/2006 8:13:15 AMAPART
Clint; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong looked at trim, still installing equip