Inspections for the day of: Friday, February 24, 2006.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00192 INSP-Final Inspection2/20/20062/24/20062/24/2006 5:35:22 PMAFAIL
Tested pull stations, duct smoke detectors, smoke alarms and verified Cd rating and spacing on av notification devices on the ground and first floor concourse B, the wall mounted notification appliances installed under this permit are below the min. height allowed per NFPA 72 2002 7.5.4 for the lens portion, still need to test functionality and performance of the notification devices, EOL drop, signal verification, etc.
FIR05-00193 INSP-Final Inspection2/20/20062/24/20062/24/2006 12:22:26 PMAPART
Duct smoke detector tested okay, verified av Cd ratings and spacing, the functionality test pending after hours inspection for audibility and performance, the av's in the adjacent hall are below min. height requirements for the strobe lens.