Inspections for the day of: Tuesday, February 24, 2009.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01451 FIRE-Final Inspection2/23/20092/24/20092/25/2009 10:28:55 AMAFAIL
Life safety items are ok. Just waiting for the fire alarm resubmittals which were required due to changes/additional devices.
BLD06-01450 FIRE-Final Inspection2/23/20092/24/20092/25/2009 10:28:13 AMAFAIL
Life safety items are ok. Just waiting for the fire alarm resubmittals which were required due to changes/additional devices.
FIR07-01051 INSP-Sprinkler Rough-in2/23/20092/24/20092/25/2009 6:57:09 AMADONE
The inspection was for the arm over/drops on the second floor. All of the arm over/drops are ok but it appears that a rough-in inspection for the main/branchline piping has not been performed. At this inspection I did not see a computer entry or markings on the plans indicating the inspection. Due to time limitations the fire sprinkler contractor is scheduling another inspection for tomorrow for a job site meeting to discuss this issue. I also found the second floor 2" west main did not have any earthquake bracing and a branchline located in the library had ceiling grid wire attached to it down its entire length.
FIR08-00831 INSP-Sprinkler Rough-in/Hydro2/24/20092/24/20092/24/2009 5:02:18 PMPPASS
1st Floor North Corridor Bldg B - Ok to cover
2nd Floor Bldg B Corridor - Ok to Cover

Told the fire protection contractor and general contractor that the same type of insulation arrangement would not be adequate in the rooms since the composite wood joist were deeper. The corridor joist space was almost entirely filled with insulation. In addition, the corridor joist space were much less than the 160^3 defined in NFPA 13
BLD08-02394 FIRE-Final Inspection2/23/20092/24/20092/24/2009 4:54:04 PMPCANC
due to time constraints
FIR08-00766 INSP-Sprinkler Rough-in/Hydro2/20/20092/24/20092/24/2009 1:52:40 PMPCANC
This is for cover inspection at 12" site feed at jobsite entrance and south center 12" near main bldg. Please call with time frame. Thank you Phone #: ###-#### Internet Inspection Request from: Jeff Packham Inspection cancelled from web by: Jeff Packham
FIR08-00752 INSP-Final Inspection2/24/20092/24/20092/24/2009 1:48:12 PMPPASS
permit finaled
BLD08-02101 FIRE-Final Inspection2/23/20092/24/20092/24/2009 1:47:41 PMPPASS
life safety passed
FIR08-00195 INSP-Final Inspection2/23/20092/24/20092/24/2009 1:45:19 PMPPASS
permit finaled
FIR08-00846 INSP-Final Inspection2/23/20092/24/20092/24/2009 1:37:23 PMAPASS
permit finaled
FIR08-00018 INSP-Sprinkler Rough-in/Hydro2/24/20092/24/20092/24/2009 12:13:13 PMPPASS
Ok to Cover 11th Floor Condos 1###-####
Condo 1105 will not be sheet rocked at this time. The fire protection is not completed and will need to be inspected at a later date. There are numerous ducts that pose and obstructions problems. Contractor was reminded that NO space is to be used for storage unless the fire protection system is redesigned and resubmitted.
Ok to Cover main corridor on 12th Floor
FIR08-00382 INSP-Final Inspection2/23/20092/24/20092/24/2009 12:08:34 PMPFAIL
Apparently the city approved plans have been lost. No inspection was performed.
FIR07-01032 INSP-Final Inspection2/23/20092/24/20092/24/2009 12:07:40 PMPPART
The sprinkler work is complete in both the first floor and second floor dining areas. An ok to cover was also given for the first floors nurses station. See the city approved plans for the exact area covered with todays date and my signature.
BLD07-01846 FIRE-Final Inspection2/23/20092/24/20092/24/2009 12:05:47 PMPFAIL
The project related fire alarm permit needs addressed. There are missing emergency lights in the second floor dining area and one addition light is needed see plan for location. The exit sign infront of the second floor stair access did not operate.
BLD08-02225 FIRE-Conference2/23/20092/24/20092/24/2009 9:47:40 AMADONE
I went over the life safety requirements/plan review notes with the builder.
FIR08-00103 INSP-Alarm Testing2/24/20092/24/20092/24/2009 12:00:00 AMPDONE
TRASH ROOM SMOKE DETECTOR Phone #: ###-#### Internet Inspection Request from: Robert Gobler