Inspections for the day of: Wednesday, February 24, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01092 ELE-Aging Inspection2/24/20102/24/20102/24/2010 3:59:44 PMPDONE
bob this work is all complet pending your sign off. 301 no activity, see doc expire
ELE09-01092 DOC - Permit Expired2/24/20102/24/20102/24/2010 3:59:07 PMPPASS
bob this work is all complet pending your sign off. 301 no activity, ok to doc expire
ELE10-00234 Final2/24/20102/24/20102/24/2010 3:56:32 PMPPASS
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called, ok to final, signed card, no esc this project
ELE10-00263 Final2/24/20102/24/20102/24/2010 3:34:04 PMPPASS
Greg Phone #: ###-#### corrections made, called, ok to final
ESC05-01650 General Inspection2/24/20102/24/20102/24/2010 3:02:56 PMPPASS
looked ok
ELE10-00062 Final2/24/20102/24/20102/24/2010 2:16:05 PMPFAIL
Contact: Paul Cushing before going Inspection requested from web by: Deb Gooden Phone #: ###-#### called, left correction notice, NEC 210.70(C) shall provide switched lighting outlet in pump hpuse, 110.22(A) shall identify disconnecting means with sufficient durability to withstand environment, 408.4 shall provide circuit directories, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-00062 Electrical Rough-In2/24/20102/24/20102/24/2010 1:41:57 PMPPASS
Contact: Paul Cushing before going Inspection requested from web by: Deb Gooden Phone #: ###-#### ok to cover u/g to sign only
ELE10-00130 Final2/24/20102/24/20102/24/2010 1:31:16 PMPPASS
keith Phone #: ###-#### ok to final, no esc this project
ELE10-00283 Rough-In Permanent Service2/24/20102/24/20102/24/2010 12:55:29 PMPPASS
keith Phone #: ###-#### ric ok, p/s u/g n ok, no esc this project
ELE10-00361 Final2/23/20102/24/20102/24/2010 10:42:38 AMAPASS
Please call me so i can meet you there. Thank You Dave Shifflett Inspection requested from web by: jason shifflett Phone #: ###-#### ok to final, no esc this project
ELE10-00361 Permanent Service2/24/20102/24/20102/24/2010 10:10:13 AMAPASS
Please call me so i can meet you there. Thank You Dave Shifflett Inspection requested from web by: jason shifflett Phone #: ###-#### p/s o/h rec ok, no esc this project
ELE09-02374 Final2/23/20102/24/20102/24/2010 9:51:45 AMAPASS
Inspection requested from web by: Scott Campbell Phone #: ###-#### ok to final, no esc this project
ELE10-00352 Electrical Rough-In2/23/20102/24/20102/24/2010 9:17:23 AMAFAIL
Jim Phone #: ###-#### called, left correction notice, NEC shall provide outlets and spacing in exposed walls and front receptacle, BCC shall change room count to 8 on elect permit, NOTE corrections shall be made within 5 working days or further action will be taken, no esc this project
ELE10-00349 Temporary Service2/22/20102/24/20102/24/2010 9:13:52 AMAPASS
Inspection requested from web by: Bob Glenn Phone #: ###-#### t/s u/g n ok, no esc this project
ELE09-02441 Electrical Rough-In2/23/20102/24/20102/24/2010 9:12:51 AMAFAIL
tony ###-#### called, left message, left correction notice, NEC 330.30(B) mc shall be secured within 12" of box, 300.4(A)(D) edge of holes and cable shall be 1 1/4" from edge of framing members,BCC shall not secure cable inside valley steel stud, shall terminate cable in box NOTE shall make corrections within 5 working days or further action will be taken