Inspections for the day of: Thursday, February 24, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00175 INSP-Final Inspection2/24/20112/24/20112/24/2011 3:26:47 PMPPASS
Permit finaled
FIR09-00084 INSP-Final Inspection2/24/20112/24/20112/24/2011 3:26:20 PMPPASS
Permit finaled
FIR10-00514 INSP-Conference2/23/20112/24/20112/24/2011 2:31:25 PMACANC
Duplicate inspection
FIR10-00514 INSP-Sprinkler Rough-in2/23/20112/24/20112/24/2011 2:31:06 PMAPASS
Todays inspection was verifying that the combustible concealed spaces around the building have been reduced in size to be less than 160 cubic feet each as allowed in the 2009 NFPA 13. All of the spaces that were spot check on the outside of the building were 120 cubic feet or less and the second floor spaces were around 80 cubic feet. I gave the ok to re-cover the concealed spaces.
BLD11-00053 FIRE-Final Inspection2/23/20112/24/20112/24/2011 11:08:34 AMPPASS
Life safety passed.