FIR09-00175
| INSP-Final Inspection | 2/24/2011 | 2/24/2011 | 2/24/2011 3:26:47 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00084
| INSP-Final Inspection | 2/24/2011 | 2/24/2011 | 2/24/2011 3:26:20 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00514
| INSP-Conference | 2/23/2011 | 2/24/2011 | 2/24/2011 2:31:25 PM | A | CANC |
|
|
Duplicate inspection
|
FIR10-00514
| INSP-Sprinkler Rough-in | 2/23/2011 | 2/24/2011 | 2/24/2011 2:31:06 PM | A | PASS |
|
|
Todays inspection was verifying that the combustible concealed spaces around the building have been reduced in size to be less than 160 cubic feet each as allowed in the 2009 NFPA 13. All of the spaces that were spot check on the outside of the building were 120 cubic feet or less and the second floor spaces were around 80 cubic feet. I gave the ok to re-cover the concealed spaces.
|
BLD11-00053
| FIRE-Final Inspection | 2/23/2011 | 2/24/2011 | 2/24/2011 11:08:34 AM | P | PASS |
|
|
Life safety passed.
|