Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00550 INSP-Final Inspection2/23/20122/24/20122/24/2012 5:29:23 PMPPART
Completed satisfactory retest of the elevator control functions after repairs made including the lobbies, pit and hoistway devices. Also finished acceptable testing of fire sprinkler monitoring including floor control valves, fire pump, MP station.
FIR11-00659 INSP-Sprinkler Rough-in/Hydro2/24/20122/24/20122/24/2012 5:24:03 PMPDEFR
Intended for hydrostatic testing of the new system supply main.
FIR12-00097 INSP-Final Inspection2/23/20122/24/20122/24/2012 5:20:02 PMAFAIL
Noted missing appliances at two locations shown on plans as existing within the remodel area, overspacing at the new A/V adjusted while on site.
FIR12-00020 INSP-Sprinkler Rough-in2/23/20122/24/20122/24/2012 5:15:06 PMAPART
UG fire supply line IBR only approved for cover at this time.
FIR12-00045 INSP-Sprinkler Rough-in2/23/20122/24/20122/24/2012 5:14:19 PMAFAIL
Correction items include painted upright sprinklers at several locations, missing two uprights per plan at the stock room area, pendent heads above the cooler may need to be relocated due to equipment changes.