Inspections for the day of: Monday, February 24, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00764 Final2/20/20142/24/20142/25/2014 8:55:01 AMPPASS
IMPORTANT!! Call Mark Reed PRIOR to inspection at ###-####. Will have to arrange for entrance into site. Phone #: ###-#### >> Inspection requested via web by Scott Campbell see 2/25/ 14 response, final ok
ELE13-03327 Final2/24/20142/24/20142/24/2014 3:03:40 PMPPART
Carl Phone #: ###-#### called, NEC 408.4 shall provide circuit directory, 210.8(B)(5) shall provide gfci for receptacle by mop sink, 253,30(A) shall strap pvc within 3' of termination, 110.26 shall provide work space about equipment, 314.25 shall provide covers for boxes, shall provide correct polarity for receptacles, signed t/o card
ELE14-00434 Electrical Rough-In2/24/20142/24/20142/24/2014 2:09:22 PMPPASS
need a soffit inspection. Phone #: ###-#### >> Inspection requested via web by Ben Archibald soffits only ok cover
ELE14-00234 Final2/24/20142/24/20142/24/2014 1:58:45 PMPPASS
Phone #: ###-#### >> Inspection requested via web by robert feller ok final, signed card
ELE14-00413 Permanent Service2/20/20142/24/20142/24/2014 1:00:03 PMPPASS
Service upgrade. Phone #: ###-#### >> Inspection requested via web by Eric Schroeder p/s o/h rec ok
ELE14-00408 Permanent Service2/21/20142/24/20142/24/2014 12:20:02 PMPPASS
Service change. 200A to 400A. Idaho Power dropping power 1st thing in A.M.
Anticipating 2-3 Hr. swap out. Possible ready before noon. Idaho Power to hook up early afternoon. Lynn Solmon/ Elektra Services ###-####. Phone #: ###-#### >> Inspection requested via web by Lynn Solmon p/s rec u/g ok
ELE11-02445 ELE-Aging Inspection2/24/20142/24/20142/24/2014 10:14:21 AM DONE
still under construction
ELE12-01757 DOC - Permit Expired2/24/20142/24/20142/24/2014 9:43:40 AMAPASS
ok doc expire, no action
ELE12-00909 Final2/24/20142/24/20142/24/2014 9:39:58 AMAPASS
ok final
ELE12-00920 Final2/24/20142/24/20142/24/2014 9:37:29 AMAPASS
ok final
ELE13-03457 Final2/24/20142/24/20142/24/2014 9:34:55 AMAPASS
Gar code 9165 Phone #: ###-#### >> Inspection requested via web by Greg Traudt corrections made, ok final
ELE14-00432 Electrical Rough-In2/24/20142/24/20142/24/2014 8:04:03 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Dan Hobdey ri ok garage only, u/g ok cover house to garage