Inspections for the day of: Wednesday, February 24, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02123 ELE-Aging Inspection2/24/20162/24/20162/24/2016 4:10:11 PM PASS
Drove by and inspected
ELE13-02123 Final2/24/20162/24/20162/24/2016 4:09:58 PMPPASS
Listing and disconnecting means confirmed. Final ok
ELE11-00099 ELE-Aging Inspection2/24/20162/24/20162/24/2016 3:44:45 PM PASS
Owner refusing to comply
ELE15-03328 Final2/24/20162/24/20162/24/2016 3:42:56 PMPFAIL
Tom Phone #: ###-####
352.30- PVC conduit shall be secured with in 3' of boxes. Ground shall not be only method.
ELE16-00366 Final2/24/20162/24/20162/24/2016 3:10:09 PMPPASS
Judy// please call before Phone #: ###-#### Faceless GFCI units located ajacent to tub. Final ok
ELE16-00366 Electrical Rough-In2/24/20162/24/20162/24/2016 2:59:50 PMPPASS
Judy// please call before Phone #: ###-#### Circuits to tub rough in ok cover
ELE15-03906 Final2/23/20162/24/20162/24/2016 2:37:49 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jonathan Poot
BCC 4-05 15- Electrical installations shall be done be a electrical contractor or journeyman employed by contractor. Basement bath floor heat installed by tile installer. Need in writing contractor to take responsiblity for floor heat installation and GFCI protection.
410.16- Recessed closet luminaires shall have totally enclosed lamps.
422.30- Hard wired kitchen appliances shall have a disconnecting means. 110.25 lock outs acceptable.
Called and left message.
ELE16-00536 Electrical Rough-In2/23/20162/24/20162/24/2016 2:00:00 PMPCANC
Larry Phone #: ###-####
Contractor called and asked to cancel
ELE16-00544 Final2/24/20162/24/20162/24/2016 12:17:41 PMPFAIL
Matt Murrey is contact at ###-####. thank you
temp power for const. trailer. Phone #: ###-#### Inspection requested via web by Debby Pierce
*Where outside perimeter of job trailer...
If PVC ran on top of grade shall be SCH 80 as per 352.10(F).
If PVC ran under ground shall comply with 300.5 18" deep.
Sch. 40 used and covered by 2" sand at time of inspection.
ELE15-03927 Final2/23/20162/24/20162/24/2016 10:43:59 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson Final ok
ELE16-00540 Electrical Rough-In2/23/20162/24/20162/24/2016 10:40:13 AMPCANC
Call-Butch Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld Inspection cancelled from web by: Daniel Schaffeld
ELE16-00008 Electrical Rough-In2/24/20162/24/20162/24/2016 9:49:35 AMAPASS
Rock

I will be onsite around 8:30 I have a bath fan to wire that was set yesterday afternoon.

Call me with any questions
Mike
B ; B
###-#### Phone #: ###-#### Inspection requested via web by Mike Cole Office and bath walls and hard lids rough in ok cover
ELE15-03298 Final2/24/20162/24/20162/24/2016 9:18:45 AMAPASS
This house Is Ready For A Final Key Is Under Small Trash Can Next To Side Door Under Car Port Please call With Any Questions Od Concerns Thanks Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett
Kitchen cabinets not set but if installed as drawn ok. Final ok
ELE16-00325 Electrical Rough-In2/23/20162/24/20162/24/2016 8:42:01 AMAPASS
Underground Conduit Inspection Request. Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence Under slab rough in ok cover
ELE15-03927 Final2/23/20162/24/20162/23/2016 3:40:55 PMACANC
access 8800 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson