Inspections for the day of: Wednesday, February 24, 2016.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC16-00671 Final2/23/20162/24/20162/24/2016 4:30:48 PMPPASS
Call Rudy when on your way, ###-#### Phone #: ###-#### Inspection requested via web by John Bertram
MEC15-05466 Final2/24/20162/24/20162/24/2016 3:34:07 PMPPASS
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
MEC16-00808 Final2/23/20162/24/20162/24/2016 3:11:26 PMPFAIL
call Betty first ###-####, this is the one right now permitted and horizon installed -
1) pad for a/c is to small, needs to extend to the edge of the equipment on all sides
2) Fuses for a/c are over sized
3) Need a electrical service switch at the furnace
4) Need to pipe condensate to a approved location
MEC16-00572 Pressure Test2/23/20162/24/20162/24/2016 2:39:09 PMPPASS
Call Jason with any issues @ 412.6696 - Thank you!! Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek - 20lb gas 5lb flue
MEC16-00572 Rough-in2/23/20162/24/20162/24/2016 2:37:36 PMPPASS
Call Jason with any issues @ 412.6696 - Thank you!! Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
MEC16-00583 Pressure Test2/23/20162/24/20162/24/2016 2:33:47 PMPPASS
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day - 20lb gas 5lb flue
MEC16-00583 Rough-in2/23/20162/24/20162/24/2016 2:32:58 PMPPASS
Please call Daryl with any questions. Phone #: ###-#### Inspection requested via web by Diane Day
MEC16-00820 Conference2/24/20162/24/20162/24/2016 1:39:06 PMPPASS
Mid PM. Please call Dave ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Xanti Berria
MEC16-00595 Rough-in2/23/20162/24/20162/24/2016 1:09:38 PMPFAIL
Tom-would like to have just after lunch if possible Phone #: ###-#### - Need approved manual J onsite, need r/a transfer in master bedroom
MEC16-00746 Rough-in2/23/20162/24/20162/24/2016 9:07:27 AMAPART
Steve/###-####/light test Phone #: ###-#### Inspection requested via web by Crystal Grant - light test pass on 2 10' long sections that were on the ground
MEC16-00457 Pressure Test2/23/20162/24/20162/24/2016 9:03:39 AMAPASS
RYAN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER - 100lb hydronic piping pass to 2 vavs
MEC14-05206 Mec-Aging Inspection2/24/20162/24/20162/24/2016 7:38:38 AM CANC
MEC14-03147 Mec-Aging Inspection2/24/20162/24/20162/24/2016 7:38:09 AM DONE
Expired
MEC14-03147 DOC - Permit Expired2/24/20162/24/20162/24/2016 7:37:35 AMAPASS
MEC14-03168 Mec-Aging Inspection2/24/20162/24/20162/24/2016 7:36:14 AM DONE
Expired
MEC14-03168 DOC - Permit Expired2/24/20162/24/20162/24/2016 7:35:21 AMAPASS