MIS04-00063
| FIR-Final | 2/24/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | A | FAIL |
|
|
Repair exit signs. Remove thumb turns on the south and the east facing exterior doors. Provide automatic flush bolts on the main entry exit. Provide approved door hardware on the east side double doors. Provide verification on the annual inspection for the fire alarm. Provide dedicated circuit for the fire alarm panel (it appears to be on a light circuit) Lower the fire extinguisher in the riser room to 48" from finish floor to handle. Repair and test emergency lights. Repair the toilet leak. Provide covers on the electrical outlets that have been damaged. Pendant head at the base of the south stairs is obstructed by a light fixture which actually covers part of the eschouseon. Provide emergency light in stairwell. Provide permit paper work so a complete inspection can be performed. 2/25/2004 9:55:03 AM
|
FIR04-00087
| INSP-Sprinkler Rough-in/Hydro | 2/24/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | A | PART |
|
|
sprinkler piping is ok to cover 2/25/2004 9:08:48 AM
|
BLD03-01798
| FIRE-Final Inspection | 2/24/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 2/25/2004 9:10:02 AM
|
FIR04-00048
| INSP-Sprinkler Rough-in/Hydro | 2/25/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled 2/25/2004 12:38:06 PM
|
FIR04-00076
| INSP-Final Inspection | 2/25/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled 2/25/2004 3:25:45 PM
|
BLD03-03051
| FIRE-Final Inspection | 2/24/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | P | FAIL |
|
|
I spoke with Scott with DBSI and he is drafting a letter to dave miller on a time frame for the fire alarm upgrade in this strip mall. When the letter is appoved and the fire extinguisher is provided a temporary occupancy can be signed 2/25/2004 4:22:29 PM
|
FIR03-00695
| INSP-Final Inspection | 2/20/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled 2/25/2004 2:16:56 PM
|
FIR03-00695
| INSP-Final Inspection | 2/20/2004 | 2/25/2004 | 2/25/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled 2/25/2004 2:16:56 PM
|