Inspections for the day of: Friday, February 25, 2005.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00658 INSP-Alarm Testing2/18/20052/25/20052/25/2005 12:00:00 AMAFAIL
terry ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is just not ready to be tested. 2/25/2005 2:06:59 PM 2/25/2005 2:08:24 PM
FIR04-00657 INSP-Final Inspection2/23/20052/25/20052/25/2005 12:00:00 AMAFAIL
terri ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is not ready for testing. 2/25/2005 2:08:40 PM
FIR05-00051 INSP-Final Inspection2/23/20052/25/20052/25/2005 12:00:00 AMAFAIL
terri ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is not ready for testing 2/25/2005 2:08:54 PM
BLD04-00789 FIRE-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAFAIL
Provide address facing cole road. Provide fire extinguishers per review comments. Provide exit discharge lighting at north exit per plans 2/25/2005 8:42:53 AM
FIR04-00592 INSP-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAFAIL
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice

U.G. Flush OK
Failed:
1. 3/4" meter installed, (requires 1" per calcs).
2. Inspectors test failed. Line malfunction (cracked 1/2" adapter).
BLD04-02803 FIRE-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAPASS
Fire life safety finaled 2/25/2005 1:17:04 PM
BLD04-03027 FIRE-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAFAIL
Remove the manual flushbolts from the east exit. Repair exit signs. Provide approved hardware on the exit doors 2/25/2005 9:11:57 AM
BLD05-00079 FIRE-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAPASS
Fire life safety finaled 2/25/2005 9:36:23 AM
FIR04-00710 INSP-Alarm Testing2/24/20052/25/20052/25/2005 12:00:00 AMAPASS
Fire alarm finaled 2/25/2005 11:34:25 AM
FIR04-00656 INSP-Sprinkler Rough-in/Hydro2/25/20052/25/20052/25/2005 12:00:00 AMAPART
THis is for trash chutes and porte-coche. Please call 1 hour prior to arrival. Before 12:00 would be acceptable.; Phone #: ###-#### Internet Inspection Request from: Trent Bice

Prete-Coche, OK to cover. 4th floor and 2nd floor trach chutes, OK to cover.

Requested walk-thorugh on all corridors:
1. 3rd floor North end line required CPVC hanger 11'-6". (If using ring hanger, w/restraint).
2. 11/4" CPVC line in front of elevator is burned and needs replaced.
3. South half of the 1st floor needs ring hanger restraints.
BLD04-01979 FIRE-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAFAIL
Remove thumbturn from the service hall exit. Provide fire extinguisher. Provide sticker at the main exit 2/25/2005 12:22:47 PM
BLD04-02763 FIRE-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMAFAIL
Need to repair the exit light on the east side front. Could not operate the other exit signs on the existing side. Provide approved hardware on the basement door. Provide door #10 so I can verify hardware in basement. Provide current inspection tag for fire extinguisher in basement. Test emergency lighting in the existing side. I spoke to the owner at told him that the remodeled space could not be occupied until signed off. Right now merchandise is set up and its open to public. 2/25/2005 12:21:40 PM
FIR05-00060 INSP-Final Inspection2/24/20052/25/20052/25/2005 12:00:00 AMPCANC
System was not ready. Missing nozzles 2/25/2005 4:15:11 PM
FIR04-00501 INSP-Final Inspection2/25/20052/25/20052/25/2005 12:00:00 AMPPASS
Hood suppression system operated correctly 2/25/2005 3:43:42 PM
FIR05-00094 INSP-Sprinkler Rough-in2/25/20052/25/20052/25/2005 12:00:00 AMPPART
Sprinkler rough-in is ok and piping can be covered but retaining straps need to be added to the existing hangers with-in the scope of work. Looks like maybe nine are needed. 2/25/2005 3:42:02 PM
FIR04-00358 INSP-Sprinkler Rough-in2/25/20052/25/20052/25/2005 12:00:00 AMPPART
See approved plans for locations in basement where the sprinkler piping is ok to cover. 2/25/2005 3:28:01 PM
BLD04-01222 FIRE-Final Inspection2/25/20052/25/20052/25/2005 12:00:00 AMPPASS
Fire life safety finaled 2/25/2005 1:57:49 PM
BLD04-01836 FIRE-Final Inspection2/25/20052/25/20052/25/2005 12:00:00 AMPCANC
To be rescheduled for monday morning 2/25/2005 4:01:38 PM
BLD04-00789 FIRE-Final Inspection2/25/20052/25/20052/25/2005 12:00:00 AMPPART
A temporary occupancy was given until I'm provided with the outdoor list for the discharge light or the light is changed to an outdoor listed. 2/25/2005 1:40:10 PM
BLD05-00234 FIRE-Conference2/25/20052/25/20052/25/2005 12:00:00 AMPDONE
I spoke with the contractor about life safety items. I told them to remove the hardware from the double doors into the dark room, there is a second available exit and to remove the manual bolts from the double doors into the laser room. Fire extinguishers need current inspection tag. One exit sign needs repaired. 2/25/2005 4:00:52 PM
FIR04-00643 INSP-Supply line flush2/24/20052/25/20052/25/2005 12:00:00 AMPPART
Inspection was for the underground hydro test which passed. 2/25/2005 2:32:15 PM