FIR04-00658
| INSP-Alarm Testing | 2/18/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
terry ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is just not ready to be tested. 2/25/2005 2:06:59 PM 2/25/2005 2:08:24 PM
|
FIR04-00657
| INSP-Final Inspection | 2/23/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
terri ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is not ready for testing. 2/25/2005 2:08:40 PM
|
FIR05-00051
| INSP-Final Inspection | 2/23/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
terri ###-#### Fire alarm is not ready for inspection. Fire pump controler handle has been broken. Fire pump is in phase reversal (running backwards). Elevator car 2 was not ready for recall testing. No sprinkler heads on second floor. Items tested are phones, battery loss, ac loss, pull stations in basement and first floor, loss of power at pump, pump running and phase reversal. System is not ready for testing 2/25/2005 2:08:54 PM
|
BLD04-00789
| FIRE-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
Provide address facing cole road. Provide fire extinguishers per review comments. Provide exit discharge lighting at north exit per plans 2/25/2005 8:42:53 AM
|
FIR04-00592
| INSP-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice
U.G. Flush OK
Failed:
1. 3/4" meter installed, (requires 1" per calcs).
2. Inspectors test failed. Line malfunction (cracked 1/2" adapter).
|
BLD04-02803
| FIRE-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/25/2005 1:17:04 PM
|
BLD04-03027
| FIRE-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
Remove the manual flushbolts from the east exit. Repair exit signs. Provide approved hardware on the exit doors 2/25/2005 9:11:57 AM
|
BLD05-00079
| FIRE-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/25/2005 9:36:23 AM
|
FIR04-00710
| INSP-Alarm Testing | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 2/25/2005 11:34:25 AM
|
FIR04-00656
| INSP-Sprinkler Rough-in/Hydro | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | PART |
|
|
THis is for trash chutes and porte-coche. Please call 1 hour prior to arrival. Before 12:00 would be acceptable.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
Prete-Coche, OK to cover. 4th floor and 2nd floor trach chutes, OK to cover.
Requested walk-thorugh on all corridors:
1. 3rd floor North end line required CPVC hanger 11'-6". (If using ring hanger, w/restraint).
2. 11/4" CPVC line in front of elevator is burned and needs replaced.
3. South half of the 1st floor needs ring hanger restraints.
|
BLD04-01979
| FIRE-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
Remove thumbturn from the service hall exit. Provide fire extinguisher. Provide sticker at the main exit 2/25/2005 12:22:47 PM
|
BLD04-02763
| FIRE-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | A | FAIL |
|
|
Need to repair the exit light on the east side front. Could not operate the other exit signs on the existing side. Provide approved hardware on the basement door. Provide door #10 so I can verify hardware in basement. Provide current inspection tag for fire extinguisher in basement. Test emergency lighting in the existing side. I spoke to the owner at told him that the remodeled space could not be occupied until signed off. Right now merchandise is set up and its open to public. 2/25/2005 12:21:40 PM
|
FIR05-00060
| INSP-Final Inspection | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | CANC |
|
|
System was not ready. Missing nozzles 2/25/2005 4:15:11 PM
|
FIR04-00501
| INSP-Final Inspection | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly 2/25/2005 3:43:42 PM
|
FIR05-00094
| INSP-Sprinkler Rough-in | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | PART |
|
|
Sprinkler rough-in is ok and piping can be covered but retaining straps need to be added to the existing hangers with-in the scope of work. Looks like maybe nine are needed. 2/25/2005 3:42:02 PM
|
FIR04-00358
| INSP-Sprinkler Rough-in | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | PART |
|
|
See approved plans for locations in basement where the sprinkler piping is ok to cover. 2/25/2005 3:28:01 PM
|
BLD04-01222
| FIRE-Final Inspection | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 2/25/2005 1:57:49 PM
|
BLD04-01836
| FIRE-Final Inspection | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | CANC |
|
|
To be rescheduled for monday morning 2/25/2005 4:01:38 PM
|
BLD04-00789
| FIRE-Final Inspection | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | PART |
|
|
A temporary occupancy was given until I'm provided with the outdoor list for the discharge light or the light is changed to an outdoor listed. 2/25/2005 1:40:10 PM
|
BLD05-00234
| FIRE-Conference | 2/25/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | DONE |
|
|
I spoke with the contractor about life safety items. I told them to remove the hardware from the double doors into the dark room, there is a second available exit and to remove the manual bolts from the double doors into the laser room. Fire extinguishers need current inspection tag. One exit sign needs repaired. 2/25/2005 4:00:52 PM
|
FIR04-00643
| INSP-Supply line flush | 2/24/2005 | 2/25/2005 | 2/25/2005 12:00:00 AM | P | PART |
|
|
Inspection was for the underground hydro test which passed. 2/25/2005 2:32:15 PM
|