ELE06-02092
| Final | 2/25/2008 | 2/25/2008 | 2/25/2008 4:31:28 PM | P | PASS |
|
|
ok to final
|
ELE07-03307
| Electrical Rough-In | 2/22/2008 | 2/25/2008 | 2/25/2008 3:39:28 PM | P | PART |
|
|
CONTACT: NEIL RAMSEY - ROUGH IN 5TH FLOOR DECK AREA PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden 5th floor deck ok to pour, reviewed several areas of job for progression, plans still being revised
|
ELE07-03784
| Final | 2/25/2008 | 2/25/2008 | 2/25/2008 2:34:39 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman corrections made, signed occupancy card, ok to final
|
ELE07-02179
| Electrical Rough-In | 2/25/2008 | 2/25/2008 | 2/25/2008 1:40:37 PM | P | FAIL |
|
|
nathan-please call at least 30 mins prior to inspection Phone #: ###-#### met owner, left correction notice NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 300.14 shall provide 6" free conductor length in box for splice connection point, 110.12(C) there shall be no broken parts (box knockouts), 110.3(B) listed equipment shall be instslled per manufacturer's instructions- no loose crimps, 334.30 nm cable shall be stapled or secured within 8" of box, 210.52(A)(2) shall provide receptacle in 2" wall space, BCC no violations shall be retained
|
ELE08-00452
| Final | 2/25/2008 | 2/25/2008 | 2/25/2008 12:50:05 PM | P | PASS |
|
|
pat Phone #: ###-#### ok to final
|
ELE08-00452
| Electrical Rough-In | 2/25/2008 | 2/25/2008 | 2/25/2008 12:49:56 PM | P | PASS |
|
|
pat Phone #: ###-#### ric ok
|
ELE06-00925
| Final | 2/25/2008 | 2/25/2008 | 2/25/2008 10:44:31 AM | A | PASS |
|
|
ok to final
|
ELE06-03501
| Final | 2/25/2008 | 2/25/2008 | 2/25/2008 9:47:13 AM | A | PASS |
|
|
ok to fnal
|
ELE08-00417
| Conference | 2/20/2008 | 2/25/2008 | 2/25/2008 9:14:57 AM | A | DONE |
|
|
Todd Phone #: ###-#### met owner, talked about service change, getting illegal sub-panels either abandoned or converted to junction boxes, grounding, panel height, stapling, accessible junction boxes,
|
ELE08-00415
| Electrical Rough-In | 2/20/2008 | 2/25/2008 | 2/25/2008 8:16:58 AM | A | CANC |
|
|
justin Phone #: ###-#### see conference
|
ELE08-00415
| Conference | 2/25/2008 | 2/25/2008 | 2/25/2008 8:16:42 AM | A | DONE |
|
|
justin Phone #: ###-#### met contractor, explained that all permits shall be pulled, approved set of plans shall be on job, before work starts, service change will require bringing electrical up to code for areas being worked on
|