Inspections for the day of: Thursday, February 25, 2010.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00376 Permanent Service2/25/20102/25/20102/26/2010 8:48:10 AMPPASS
Rocky-Please call at least 30 mins prior to inspection Phone #: ###-#### p/s o/h rec. ok
ELE10-00241 Electrical Rough-In2/25/20102/25/20102/26/2010 8:16:42 AMPPASS
The rough in inspection is for the ceiling. If it is satisfactory can we also get a final for the project. Walls and ceiling. Inspection requested from web by: Justin Fratesok
ELE10-00104 Conference2/22/20102/25/20102/25/2010 4:34:55 PMPDONE
Luke-After 3:30 please-call first please Phone #: ###-#### ok
ELE10-00004 Permanent Service2/24/20102/25/20102/25/2010 4:34:27 PMPPASS
Inspection requested from web by: BARRY KENDALL Phone #: ###-#### p/s o/h rec. ok 2 meters
ELE10-00304 Final2/25/20102/25/20102/25/2010 2:42:24 PMPNR
paul Phone #: ###-#### called needs r/i , ele permit attached to bld permit contr will reschedule
ELE10-00382 Electrical Rough-In2/25/20102/25/20102/25/2010 1:53:29 PMPFAIL
Inspect floor heat. Please call ahead so the contractor can let you in the home. Inspection requested from web by: Brandon Blackham Phone #: ###-####
corr. posted called 110.3(B) shall follow manufactures instructions for floor heat and plastic boxes no metallic fittings or mudrings
ELE10-00375 Permanent Service2/24/20102/25/20102/25/2010 1:07:53 PMACANC
matt Phone #: ###-#### see added r/i
ELE10-00375 Electrical Rough-In2/25/20102/25/20102/25/2010 1:07:24 PMPPART
matt Phone #: ###-#### a/c ok still needs gfci inuse cover recept for a/c and wire exhaust fans called
ELE10-00045 Rough-In Permanent Service2/24/20102/25/20102/25/2010 12:27:44 PMAPASS
inspection for both 2806 and 2952. Inspection requested from web by: Alan Lusk Phone #: ###-#### r/i p/s u/g new ok
ELE10-00362 Electrical Rough-In2/24/20102/25/20102/25/2010 11:00:53 AMAPASS
Inspection requested from web by: daniel bibikov Phone #: ###-#### ok
ELE10-00316 Rough-In Permanent Service2/25/20102/25/20102/25/2010 10:23:48 AMAFAIL
Thank you ! Inspection requested from web by: Tracy Robertson Phone #: ###-####
see added p/s, called corr posted 314.20 ouyside boxes shall be flush with siding, 200.6&7 reidentify with wire used as switchleg, 110.14(B) needs devices for all equip grd splices, B C C complete all makeup,
ELE10-00316 Permanent Service2/25/20102/25/20102/25/2010 10:16:16 AMAPASS
Thank you ! Inspection requested from web by: Tracy Robertson Phone #: ###-####
p/s u/g new ok
ELE10-00351 Electrical Rough-In2/24/20102/25/20102/25/2010 9:10:15 AMAPART
darrin Phone #: ###-#### walls and ceiling new lab
ELE10-00355 Electrical Rough-In2/25/20102/25/20102/25/2010 9:00:34 AMAFAIL
Please inspect the Light fixtures and we alsp installed some Outlets. Please contact Vince at ###-#### with questions. Inspection requested from web by: Clint Tate Phone #: ###-#### corr called shall attach ele permit to bld permit, BCC romex not allowed, 300.11 and 314.23(D)(2) install support wires for box and MC wiring for new light fixture, 400.8(5) remove recept and cords from above ceiling grid
ELE08-02292 ELE-Aging Inspection2/25/20102/25/20102/25/2010 7:29:09 AM CANC
ELE08-02292 DOC - Permit Expired2/25/20102/25/20102/25/2010 7:29:02 AMAPASS
no activity
ELE08-02258 ELE-Aging Inspection2/25/20102/25/20102/25/2010 7:27:55 AM CANC
ELE08-02258 DOC - Permit Expired2/25/20102/25/20102/25/2010 7:27:52 AMAPASS
no avtivity