Inspections for the day of: Friday, February 25, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00143 FIR-Aging Inspection2/25/20112/25/20113/1/2011 3:45:26 PM NR
I spoke to Brian with Lightning Electric about the job status
FIR10-00274 INSP-Final Inspection2/25/20112/25/20112/25/2011 2:53:36 PMPFAIL
Provide as-builts and map for the facp with the correct device addressing.
FIR11-00062 INSP-Final Inspection2/25/20112/25/20112/25/2011 2:49:55 PMPPASS
permit finaled
FIR10-00541 INSP-Final Inspection2/24/20112/25/20112/25/2011 2:13:58 PMPFAIL
No testing was actually performed. The pull station is required to be relocated as per the approved plans. Not addressed on the plans was the requriement for audibility in the new open office and in the pharmacy. A visual device is required in the new restroom that is located within the pharmacy. Also in the reception area at the pharmacy has what appears to be an existing strobe mounted in a new wall. This device will have to meet current code for spacing or the code under which is was installed if it had not been modified.
BLD11-00276 FIRE-Final Inspection2/23/20112/25/20112/25/2011 10:01:59 AMAFAIL
Repair all exit signs and emergency lights, remove the dead bolt from the east exterior exit door and resubmit plans with a corrected floor layout.