FIR14-00643
| INSP-Final Inspection | 2/25/2015 | 2/25/2015 | 2/25/2015 3:45:11 PM | P | PASS |
|
|
Overbooked
|
FIR14-00642
| INSP-Final Inspection | 2/25/2015 | 2/25/2015 | 2/25/2015 3:44:54 PM | P | CANC |
|
|
Overbooked
|
FIR15-00054
| INSP-Sprinkler Rough-in | 2/25/2015 | 2/25/2015 | 2/25/2015 3:44:13 PM | P | CANC |
|
|
Overbooked
|
FIR14-00475
| INSP-Sprinkler Rough-in | 2/25/2015 | 2/25/2015 | 2/25/2015 3:43:53 PM | P | FAIL |
|
|
Per review comments plan modifications are needed due to pipe route changes affecting hydraulic calculations. Piping can not be covered and a re-inspection will be required.
|
BLD14-01856
| FIRE-Conference | 2/25/2015 | 2/25/2015 | 2/25/2015 3:42:31 PM | P | DONE |
|
|
Doug and I talked of options for the exterior soffit such as sprinklers or fire stopping to 160 cubic feet
|
FIR14-00541
| INSP-Final Inspection | 2/24/2015 | 2/25/2015 | 2/25/2015 3:40:42 PM | A | CANC |
|
|
Overbooked
|
FIR14-00540
| INSP-Final Inspection | 2/24/2015 | 2/25/2015 | 2/25/2015 3:40:24 PM | A | CANC |
|
|
Overbooked
|
BLD14-03342
| FIRE-Final Inspection | 2/24/2015 | 2/25/2015 | 2/25/2015 3:40:05 PM | A | CANC |
|
|
Per Scott and my conversation the Plan Mod for the original shell core needs to be approved prior to a sign off on the restraunt tenant that is utilizing indoor seating on a raised platform directly adjacent to the restraunt.
|
FIR14-00475
| INSP-Supply line flush | 2/25/2015 | 2/25/2015 | 2/25/2015 3:37:44 PM | P | CANC |
|
|
united water did not turn on water. could not perform flush
|
FIR15-00045
| INSP-Final Inspection | 2/24/2015 | 2/25/2015 | 2/25/2015 2:41:18 PM | P | FAIL |
|
|
Hood suppression system functioned correctly but no fire alarm interconnection permit has been applied for. This permit will be ok to final when interconnection has been tested.
|
FIR14-00947
| INSP-Final Inspection | 2/23/2015 | 2/25/2015 | 2/25/2015 2:40:06 PM | P | FAIL |
|
|
Everything is ok except the insulation at the new duct/roof penatrations needs to be repaired.
|
BLD14-03582
| FIRE-Final Inspection | 2/25/2015 | 2/25/2015 | 2/25/2015 1:53:26 PM | P | FAIL |
|
|
The existing exit sign at the inner main doors does not stay lighted when tested. All other items corrected
|
BLD15-00359
| FIRE-Final Inspection | 2/25/2015 | 2/25/2015 | 2/25/2015 1:06:56 PM | P | FAIL |
|
|
Still need to address fire extinguishers and door hardware. See notes on plan
|
FIR15-00123
| INSP-Final Inspection | 2/24/2015 | 2/25/2015 | 2/25/2015 12:26:15 PM | P | PASS |
|
|
permit finaled
|
FIR14-00602
| INSP-Sprinkler Rough-in/Hydro | 2/24/2015 | 2/25/2015 | 2/25/2015 9:31:51 AM | A | PART |
|
|
OH/Hydro inspection failed. Rough to cover on remaining ceilings passed. I noted one pendant needs an additional hanger.
|
NAF15-00003
| INSP-Final | 2/20/2015 | 2/25/2015 | 2/25/2015 9:31:03 AM | A | FAIL |
|
|
No sheet rock/ceilings, no paint, no sprinkler canopies. No inspection performed.
|
BLD15-00410
| FIRE-Final Inspection | 2/24/2015 | 2/25/2015 | 2/25/2015 9:27:09 AM | A | PASS |
|
|
life safety passed
|