Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02845 Conference2/25/20162/25/20162/25/2016 4:19:47 PMPDONE
Shawn Phone #: ###-####
Discussed different new meter bases that are available for subfeed interior panel. Grounding electrodes relocating to new service location, looked at sample pop up receptacle assembly for islant counter top, no tamper, no listing. revisted bathroom receptacle requirements
ELE13-01434 ELE-Aging Inspection2/25/20162/25/20162/25/2016 3:48:52 PM PASS
Tried to drive by but could not locate address. Waiting on contractor
ELE16-00069 Final2/25/20162/25/20162/25/2016 2:49:13 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
314.20- Boxes in walls with tile set back 1/4" or more shall have an extension ring.101, 102, 202.
Boxes in combustible walls shall be flush or have an extension ring. Micro 102.
408.4- Circuit breakers shall be specifically identify purpose. breaker marked trans= living, kitchen lts, hall.
ELE15-04059 Final2/25/20162/25/20162/25/2016 2:00:55 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
314.20- Boxes mounted in tile that are set back 1/4" or more shall have as extensiion ring installed.
406.6- Receptacle face plate shall be installed to cover opening. 202 disposal.
408.4- Circuit breakers shall be specifically identify purpose. Trans= living, kitchen lts, hall.
ELE16-00287 Final2/25/20162/25/20162/25/2016 1:17:14 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender
Final ok
ELE15-03328 Final2/25/20162/25/20162/25/2016 12:52:31 PMPPASS
Tom Phone #: ###-#### Final ok
ELE15-03712 Electrical Rough-In2/24/20162/25/20162/25/2016 12:07:23 PMAPASS
Please rough inspect the Lid only of the warehouse portion of this project. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot
Rough in ok cover
ELE16-00430 Electrical Rough-In2/24/20162/25/20162/25/2016 11:44:03 AMAPASS
Rick-underground conduit-late AM Phone #: ###-#### Underground under road. 4 install for electrical with spare and sleeve for future sprinkler. Rough in ok cover
ELE16-00559 Final2/24/20162/25/20162/25/2016 11:21:08 AMAFAIL
Shop Service. Enter through double gate at side of house driveway and shop man door is unlocked and accessible. Phone #: ###-#### Inspection requested via web by Clay Jackson
Needed permenant service inspection.
4
BCC 4-05-32 Code violations not to be retained.
400.8- Flexible cords shall not be used in place of permenant wiring of structure.
334.30- NM cable shall be secured with in 12" of boxes and luminaires.
300.3(A)- single conductors shall be installed in a conduit or listed cable assembly.
ELE16-00559 Permanent Service2/25/20162/25/20162/25/2016 11:16:53 AMPPASS
Shop Service. Enter through double gate at side of house driveway and shop man door is unlocked and accessible. Phone #: ###-#### Inspection requested via web by Clay Jackson
p/s u/g n ok
ELE16-00555 Electrical Rough-In2/24/20162/25/20162/25/2016 10:35:43 AMAPASS
Final inspection needed as well Phone #: ###-#### Inspection requested via web by Stuart Welton Heater rough in ok
ELE16-00555 Final2/25/20162/25/20162/25/2016 10:35:22 AMPPASS
Final inspection needed as well Phone #: ###-#### Inspection requested via web by Stuart Welton Final ok
ELE16-00555 Electrical Rough-In2/25/20162/25/20162/25/2016 10:34:53 AMPPASS
Final inspection needed as well Phone #: ###-#### Inspection requested via web by Stuart Welton
Heater rough in ok
ELE16-00291 Final2/24/20162/25/20162/25/2016 9:47:35 AMAPASS
John Phone #: ###-#### Labels ok no hot tub on site. Final ok
ELE16-00560 Temporary Service2/24/20162/25/20162/25/2016 9:14:00 AMAFAIL
Phone #: ###-#### Inspection requested.
250.24- Grounding electrode system shall be connected to the grounded conductor prior to temp service.
ELE15-03396 Rough-In Permanent Service2/24/20162/25/20162/25/2016 9:11:52 AMAFAIL
Phone #: ###-#### Inspection requested via web by Stacie Tasker
110.24- Available fault current shall be posted with date calculated prior to P/S.
230.95(C)- performance test shall be performed for 1600 amp 480 service prior to P/S.
250.24- Grounding electrode system shall be connected to grounded conductor prior to P/S.
2 Spare conduits in electrical room off service bay shall be permenantly sealed as ventalation provided but vents not with in 12" of floor.
Verbal with electrical foreman.