ELE15-02845
| Conference | 2/25/2016 | 2/25/2016 | 2/25/2016 4:19:47 PM | P | DONE |
|
|
Shawn Phone #: ###-#### Discussed different new meter bases that are available for subfeed interior panel. Grounding electrodes relocating to new service location, looked at sample pop up receptacle assembly for islant counter top, no tamper, no listing. revisted bathroom receptacle requirements
|
ELE13-01434
| ELE-Aging Inspection | 2/25/2016 | 2/25/2016 | 2/25/2016 3:48:52 PM | | PASS |
|
|
Tried to drive by but could not locate address. Waiting on contractor
|
ELE16-00069
| Final | 2/25/2016 | 2/25/2016 | 2/25/2016 2:49:13 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 314.20- Boxes in walls with tile set back 1/4" or more shall have an extension ring.101, 102, 202. Boxes in combustible walls shall be flush or have an extension ring. Micro 102. 408.4- Circuit breakers shall be specifically identify purpose. breaker marked trans= living, kitchen lts, hall.
|
ELE15-04059
| Final | 2/25/2016 | 2/25/2016 | 2/25/2016 2:00:55 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 314.20- Boxes mounted in tile that are set back 1/4" or more shall have as extensiion ring installed. 406.6- Receptacle face plate shall be installed to cover opening. 202 disposal. 408.4- Circuit breakers shall be specifically identify purpose. Trans= living, kitchen lts, hall.
|
ELE16-00287
| Final | 2/25/2016 | 2/25/2016 | 2/25/2016 1:17:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
ELE15-03328
| Final | 2/25/2016 | 2/25/2016 | 2/25/2016 12:52:31 PM | P | PASS |
|
|
Tom Phone #: ###-#### Final ok
|
ELE15-03712
| Electrical Rough-In | 2/24/2016 | 2/25/2016 | 2/25/2016 12:07:23 PM | A | PASS |
|
|
Please rough inspect the Lid only of the warehouse portion of this project. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot Rough in ok cover
|
ELE16-00430
| Electrical Rough-In | 2/24/2016 | 2/25/2016 | 2/25/2016 11:44:03 AM | A | PASS |
|
|
Rick-underground conduit-late AM Phone #: ###-#### Underground under road. 4 install for electrical with spare and sleeve for future sprinkler. Rough in ok cover
|
ELE16-00559
| Final | 2/24/2016 | 2/25/2016 | 2/25/2016 11:21:08 AM | A | FAIL |
|
|
Shop Service. Enter through double gate at side of house driveway and shop man door is unlocked and accessible. Phone #: ###-#### Inspection requested via web by Clay Jackson Needed permenant service inspection. 4 BCC 4-05-32 Code violations not to be retained. 400.8- Flexible cords shall not be used in place of permenant wiring of structure. 334.30- NM cable shall be secured with in 12" of boxes and luminaires. 300.3(A)- single conductors shall be installed in a conduit or listed cable assembly.
|
ELE16-00559
| Permanent Service | 2/25/2016 | 2/25/2016 | 2/25/2016 11:16:53 AM | P | PASS |
|
|
Shop Service. Enter through double gate at side of house driveway and shop man door is unlocked and accessible. Phone #: ###-#### Inspection requested via web by Clay Jackson p/s u/g n ok
|
ELE16-00555
| Electrical Rough-In | 2/24/2016 | 2/25/2016 | 2/25/2016 10:35:43 AM | A | PASS |
|
|
Final inspection needed as well Phone #: ###-#### Inspection requested via web by Stuart Welton Heater rough in ok
|
ELE16-00555
| Final | 2/25/2016 | 2/25/2016 | 2/25/2016 10:35:22 AM | P | PASS |
|
|
Final inspection needed as well Phone #: ###-#### Inspection requested via web by Stuart Welton Final ok
|
ELE16-00555
| Electrical Rough-In | 2/25/2016 | 2/25/2016 | 2/25/2016 10:34:53 AM | P | PASS |
|
|
Final inspection needed as well Phone #: ###-#### Inspection requested via web by Stuart Welton Heater rough in ok
|
ELE16-00291
| Final | 2/24/2016 | 2/25/2016 | 2/25/2016 9:47:35 AM | A | PASS |
|
|
John Phone #: ###-#### Labels ok no hot tub on site. Final ok
|
ELE16-00560
| Temporary Service | 2/24/2016 | 2/25/2016 | 2/25/2016 9:14:00 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested. 250.24- Grounding electrode system shall be connected to the grounded conductor prior to temp service.
|
ELE15-03396
| Rough-In Permanent Service | 2/24/2016 | 2/25/2016 | 2/25/2016 9:11:52 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker 110.24- Available fault current shall be posted with date calculated prior to P/S. 230.95(C)- performance test shall be performed for 1600 amp 480 service prior to P/S. 250.24- Grounding electrode system shall be connected to grounded conductor prior to P/S. 2 Spare conduits in electrical room off service bay shall be permenantly sealed as ventalation provided but vents not with in 12" of floor. Verbal with electrical foreman.
|