Inspections for the day of: Thursday, February 26, 1998.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-03227 INSP - Electrical Rough-In2/25/19982/26/19982/26/1998 12:00:00 AMAPASS
PERM SERV OK
ELE98-00025 INSP - Electrical Rough-In2/25/19982/26/19982/26/1998 12:00:00 AMAPART
02/26/98 315 - ed pager ###-#### ok low voltage wiring corrected by AEI ceiling
ELE98-00111 INSP - Final2/25/19982/26/19982/26/1998 12:00:00 AMAPASS
02/26/98 315 - dan ###-#### re insp ok cor. made
ELE98-00587 INSP - Final2/24/19982/26/19982/26/1998 12:00:00 AMAPART
02/26/98 315 - elevator/state liquor disp/ gowen plaza #3/ ###-#### ok no 14 r/i
ELE98-00599 INSP - Electrical Rough-In2/25/19982/26/19982/26/1998 12:00:00 AMAPASS
02/26/98 315 - R/I AND PERM---BOB ###-#### 15rms 1a/c 200a
ELE98-00602 INSP - Electrical Rough-In2/26/19982/26/19982/26/1998 12:00:00 AMPPASS
02/26/98 315 - ###-#### REMODEL OF FIVE ROOMS ok 4rms res. rem. also did a conference with B&B on 2/25/98
ELE98-00214 INSP - Electrical Rough-In2/26/19982/26/19982/26/1998 12:00:00 AMPFAIL
02/26/98 315 - THIS IS FOR A GARAGE--DOOR IS OPEN--###-#### LEE cor. posted B.C.C. needs to complete r/i, 336-18 support romex at boxes, 336-30 (b) use approved cable type NM B not old type NM
ELE98-00546 INSP - Electrical Rough-In2/26/19982/26/19982/26/1998 12:00:00 AMPPASS
02/26/98 315 - PERM SERV--KAREN ###-#### ok 200a
ELE98-00574 INSP - Final2/26/19982/26/19982/26/1998 12:00:00 AMPFAIL
02/26/98 315 - jack has no number will leave unlocked cor. posted 310-15 note #8 derate for 50% conduit fill, 110-3(b) use manufactures breakers only, 250-23 isolate grds and neutrals at sub pane house, 250-81 terminate grd within 5ft of where water pipe enters