ELE06-04387
| ELE-Aging Inspection | 2/26/2007 | 2/26/2007 | 2/27/2007 12:37:44 PM | | DONE |
|
|
final added
|
ELE07-00611
| Electrical Rough-In | 2/26/2007 | 2/26/2007 | 2/26/2007 3:09:45 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 2/26/2007 at 9:44:52 AM. Contact: ###-####. ok
|
ELE06-04083
| Electrical Rough-In | 2/26/2007 | 2/26/2007 | 2/26/2007 2:29:48 PM | P | PASS |
|
|
DAVE - please call first; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i ok
|
ELE06-04314
| Final | 2/26/2007 | 2/26/2007 | 2/26/2007 2:03:44 PM | P | PASS |
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
|
ELE07-00625
| Permanent Service | 2/26/2007 | 2/26/2007 | 2/26/2007 1:11:41 PM | P | FAIL |
|
|
Call Gary ###-#### ofr access. Work performed by Joe Schneehagen. Phone #: ###-#### fee due corr. called 110.3(B) use manufactures breakers only, 110.12(A),and 408.7 seal all unused openings KOs and breaker, 300.10&12 install locknuts on all fittings and tighten all locknuts nipple between meter and paanel and fitting in back of panel, 250.64(E) use plastic or listed fitting for GEC, 40804 needs panel directory
|
ELE06-02788
| Final | 2/26/2007 | 2/26/2007 | 2/26/2007 12:30:00 PM | P | CANC |
|
|
called wrong address there is no 12805, address on house is 12803
|
ELE07-00362
| Final | 2/26/2007 | 2/26/2007 | 2/26/2007 11:59:58 AM | P | PASS |
|
|
brad; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
|
ELE07-00628
| Final | 2/23/2007 | 2/26/2007 | 2/26/2007 8:48:43 AM | A | PASS |
|
|
Work performed by Steve Johnson. Phone #: ###-#### ok
|
ELE07-00462
| Electrical Rough-In | 2/23/2007 | 2/26/2007 | 2/26/2007 8:41:25 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 2/23/2007 at 12:04:43 PM. Contact: ###-####. walls and hard ceiling ok
|
ELE07-00625
| Permanent Service | 2/23/2007 | 2/26/2007 | 2/26/2007 8:13:03 AM | A | NH |
|
|