BLD06-02655
| FIRE-Final Inspection | 2/23/2007 | 2/26/2007 | 3/1/2007 4:28:28 PM | A | PASS |
|
|
Fire life safety passed inspection, noted two covers at SD to be removed after const. cleaning is finished and prior to occupancy, contractor also agreed to remove locking hasp at the door to the mech. room while on site.
|
FIR06-00527
| FIR-Aging Inspection | 2/26/2007 | 2/26/2007 | 2/27/2007 5:56:39 PM | | DEFR |
|
|
|
BLD06-03172
| BLD-Aging Inspection | 2/26/2007 | 2/26/2007 | 2/27/2007 11:46:10 AM | P | DONE |
|
|
On site visit with Joe the building manager, work appears completed okay, no documents available on site.
|
FIR07-00100
| INSP-Sprinkler Rough-in/Hydro | 2/23/2007 | 2/26/2007 | 2/26/2007 4:27:24 PM | P | PART |
|
|
UG hydrostatic test completed satisfactory.
|
FIR07-00100
| INSP-Sprinkler Rough-in | 2/23/2007 | 2/26/2007 | 2/26/2007 4:26:18 PM | P | FAIL |
|
|
The installation does not match plan (mains re-routed, antifreeze supply point moved, heads deleted, DSW heads added, branch lines moved, etc.), 1st floor has overspaced and blocked heads at several locations, SW heads installed too low, 2nd floor has overspaced uprights, mixed temp. heads in the same fire area, blocked upright at the atrium, antifreeze install does not match plan, will require plan resubmittal reflecting actual installation.
|
FIR07-00100
| INSP-Supply line flush | 2/23/2007 | 2/26/2007 | 2/26/2007 4:14:23 PM | P | NR |
|
|
Contact is Perly @ ###-####. Thank you Phone #: ###-####
|
FIR06-00476
| INSP-Final Inspection | 2/23/2007 | 2/26/2007 | 2/26/2007 4:13:13 PM | P | PASS |
|
|
Corrections are complete, fire sprinkler permit finaled.
|
FIR06-00101
| INSP-Sprinkler Rough-in/Hydro | 2/23/2007 | 2/26/2007 | 2/26/2007 3:02:46 PM | P | CANC |
|
|
Cancel inspection per phone call from contractor.
|
FIR06-00558
| INSP-Sprinkler Rough-in | 2/26/2007 | 2/26/2007 | 2/26/2007 3:01:42 PM | P | PART |
|
|
OH rough-in is okay for cover at the areas and rooms as circled on approved plans, noted two missing heads in OR17, one damaged head in the corridor, and possible obstruction issues by the curtain track at some patient rooms.
|
FIR05-00889
| INSP-Final Inspection | 2/26/2007 | 2/26/2007 | 2/26/2007 1:56:41 PM | P | PASS |
|
|
TI Fire alarm permit finaled.
|
FIR05-00888
| INSP-Final Inspection | 2/26/2007 | 2/26/2007 | 2/26/2007 1:55:52 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR05-00695
| INSP-Final Inspection | 2/26/2007 | 2/26/2007 | 2/26/2007 1:54:51 PM | P | PASS |
|
|
Correction notice items have been completed and verified per field inspection completed by M.Timmerman. Fire Alarm Permit Finaled.
|
FIR06-00449
| INSP-Final Inspection | 2/23/2007 | 2/26/2007 | 2/26/2007 1:37:00 PM | P | FAIL |
|
|
Missing escutcheons at exterior canopy pendents.
|
FIR06-01005
| INSP-Final Inspection | 2/23/2007 | 2/26/2007 | 2/26/2007 1:35:03 PM | P | NH |
|
|
Approved plans and permit documents were not on site for inspection.
|
MIS07-00022
| FIR-Final | 2/23/2007 | 2/26/2007 | 2/26/2007 11:48:49 AM | A | PASS |
|
|
Items on c/n are complete, inspection passed.
|
FIR07-00098
| INSP-Final Inspection | 2/23/2007 | 2/26/2007 | 2/26/2007 11:47:33 AM | A | PASS |
|
|
Required corrections have been verified for completion, fire alarm permit finaled.
|
MIS07-00027
| FIR-Final | 2/23/2007 | 2/26/2007 | 2/26/2007 11:45:52 AM | A | FAIL |
|
|
Noted several items in need of correction including door hardware, emergency lighting, provide address numbers, provide fire extinguishers as discussed, signage at the main entry/exit, indicated basic requirements attatched to permit.
|
FIR06-00449
| INSP-Final Inspection | 2/23/2007 | 2/26/2007 | 2/23/2007 1:11:53 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 2/23/2007 at 1:02:01 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 23 2007 1:11PM.
|