ELE07-03939
| ELE-Aging Inspection | 2/26/2008 | 2/26/2008 | 2/28/2008 3:31:31 PM | | DONE |
|
|
suc
|
ELE08-00214
| Final | 2/26/2008 | 2/26/2008 | 2/26/2008 4:11:42 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 2/26/2008 at 7:32:26 AM. Contact: ###-####. ok to final, signed occupancy card
|
ELE08-00436
| Final | 2/26/2008 | 2/26/2008 | 2/26/2008 3:04:53 PM | P | PASS |
|
|
ok to final, signed occupancy card
|
ELE08-00436
| Electrical Rough-In | 2/25/2008 | 2/26/2008 | 2/26/2008 2:58:04 PM | P | PASS |
|
|
please inspect lights in sears footware showroom lower entrance Phone #: ###-#### Internet Inspection Request from: gary batten ok to cover ceilings
|
ELE08-00454
| Electrical Rough-In | 2/25/2008 | 2/26/2008 | 2/26/2008 1:47:44 PM | P | PASS |
|
|
Internet Inspection Request from: Randy Vail had contractor call office to change address to 1474, walls only ok to cover
|
ELE08-00463
| Electrical Rough-In | 2/26/2008 | 2/26/2008 | 2/26/2008 12:49:13 PM | P | PASS |
|
|
Bed - Bath Remodel Phone #: ###-#### Internet Inspection Request from: Lloyd Looney ric ok
|
ELE08-00355
| Final | 2/25/2008 | 2/26/2008 | 2/26/2008 10:32:35 AM | A | NH |
|
|
Danny, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, left sticker, fee due
|
ELE08-00448
| Rough-In Permanent Service | 2/25/2008 | 2/26/2008 | 2/26/2008 9:50:44 AM | A | CANC |
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek see ri and p/s
|
ELE08-00448
| Permanent Service | 2/26/2008 | 2/26/2008 | 2/26/2008 9:50:23 AM | A | PASS |
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek p/s u/g n ok
|
ELE08-00448
| Electrical Rough-In | 2/26/2008 | 2/26/2008 | 2/26/2008 9:44:31 AM | A | FAIL |
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek called contractor, left correction notice, BCC job address shall be posted, job id sticker shall be posted, boxes shall be installed for bath and micro-wave, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 334.30 nm cable shall be stapled within 12" of panel, 210.52(a)(1) receptacles shall be installed such that no point alonf wall space is over 6' from an outlet
|
ELE07-02302
| Electrical Rough-In | 2/25/2008 | 2/26/2008 | 2/26/2008 9:27:02 AM | A | PART |
|
|
CONTACT: STEVE HESS - ROUGH-IN AREA I PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden walls only anop for part of area I
|
ELE08-00194
| Final | 2/25/2008 | 2/26/2008 | 2/26/2008 8:49:15 AM | A | PASS |
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final, met contractor, signed occupancy card
|
ELE08-00194
| Electrical Rough-In | 2/25/2008 | 2/26/2008 | 2/26/2008 8:19:08 AM | A | PASS |
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover ceilings only
|