Inspections for the day of: Thursday, February 26, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00287 INSP-Alarm Testing2/26/20092/26/20092/27/2009 11:23:18 AMPFAIL
This inspection was for the Corrections tenant expansion into the new area of the first floor. NAC circuit #4 did not meet the minimum 21.6 volt requirement at the end of line. Caps were missing from the end of the sample tubes for the two duct smoke detectors tested. There have been significant changes to the notification circuits and resubmittals will be required prior to a final inspection and sign off.
FIR08-00855 INSP-Sprinkler Rough-in2/26/20092/26/20092/26/2009 4:57:34 PMPCANC
To be rescheduled per the fire sprinkler contractor.
FIR07-01051 INSP-Sprinkler Rough-in2/25/20092/26/20092/26/2009 4:56:32 PMAPASS
2nd Floor approved to cover except for 3 incomplete stairwells (stairwells highlighted on plans)
1st Floor bathrooms approved to cover and highlight on job site plans.
BLD07-02290 FIRE-Final Inspection2/26/20092/26/20092/26/2009 4:39:28 PMPFAIL
The door hardware was not completely installed and the door were locked to the apartments. The contractor was not on site. No inspection was performed.
FIR09-00023 INSP-Final Inspection2/25/20092/26/20092/26/2009 3:46:08 PMPFAIL
The smoke detectors are overspace in relation to the draft stopd and beams. Additional smoke detectors or spacing modifications are required. Provide verification of max. CFM of the existing HVAC units. See IMC 606 for duct smoke detector requirements. Provide testing of the audio/visual devices. Provide as-builts. Provide strobe coverage to meet the 16'-0" requirement fo review note #25 for residential requirements.
FIR08-00801 INSP-Final Inspection2/26/20092/26/20092/26/2009 3:33:59 PMPPASS
permit finaled
FIR09-00142 INSP-Final Inspection2/25/20092/26/20092/26/2009 3:20:07 PMAPASS
permit finaled
BLD08-01097 FIRE-Final Inspection2/25/20092/26/20092/26/2009 3:18:00 PMAFAIL
No inspection performed since the city approved plans were not on site.
BLD08-01078 FIRE-Final Inspection2/25/20092/26/20092/26/2009 11:23:13 AMAFAIL
Provide building address, repair the exit discharge light at the southeast corner and either provide correctly installed and functional duct smoke detectors or remove them.
BLD08-01783 FIRE-Final Inspection2/25/20092/26/20092/26/2009 10:26:42 AMAPASS
Fire life safety passed
BLD05-03074 FIRE-Final Inspection2/25/20092/26/20092/26/2009 10:25:19 AMAFAIL
Provide exit signs and emergency lighting as per the approved plans. Replace the round door knobs as marked on the plans with approved single action hardware.
BLD08-02487 FIRE-Final Inspection2/25/20092/26/20092/26/2009 9:46:12 AMAPASS
life safety passed
FIR07-00932 INSP-Final Inspection2/26/20092/26/20092/26/2009 8:00:29 AMPPASS
permit finaled
BLD06-01451 FIRE-Final Inspection2/25/20092/26/20092/26/2009 7:59:18 AMAPART
A temporary occupancy was given until the project related fire alarm permit is finaled. Life safety items will be ok to pass at that time.
BLD06-01450 FIRE-Final Inspection2/25/20092/26/20092/26/2009 7:58:37 AMAPART
A temporary occupancy was given until the project related fire alarm permit is finaled. Life safety items will be ok to pass at that time.