FIR08-00287
| INSP-Alarm Testing | 2/26/2009 | 2/26/2009 | 2/27/2009 11:23:18 AM | P | FAIL |
|
|
This inspection was for the Corrections tenant expansion into the new area of the first floor. NAC circuit #4 did not meet the minimum 21.6 volt requirement at the end of line. Caps were missing from the end of the sample tubes for the two duct smoke detectors tested. There have been significant changes to the notification circuits and resubmittals will be required prior to a final inspection and sign off.
|
FIR08-00855
| INSP-Sprinkler Rough-in | 2/26/2009 | 2/26/2009 | 2/26/2009 4:57:34 PM | P | CANC |
|
|
To be rescheduled per the fire sprinkler contractor.
|
FIR07-01051
| INSP-Sprinkler Rough-in | 2/25/2009 | 2/26/2009 | 2/26/2009 4:56:32 PM | A | PASS |
|
|
2nd Floor approved to cover except for 3 incomplete stairwells (stairwells highlighted on plans) 1st Floor bathrooms approved to cover and highlight on job site plans.
|
BLD07-02290
| FIRE-Final Inspection | 2/26/2009 | 2/26/2009 | 2/26/2009 4:39:28 PM | P | FAIL |
|
|
The door hardware was not completely installed and the door were locked to the apartments. The contractor was not on site. No inspection was performed.
|
FIR09-00023
| INSP-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 3:46:08 PM | P | FAIL |
|
|
The smoke detectors are overspace in relation to the draft stopd and beams. Additional smoke detectors or spacing modifications are required. Provide verification of max. CFM of the existing HVAC units. See IMC 606 for duct smoke detector requirements. Provide testing of the audio/visual devices. Provide as-builts. Provide strobe coverage to meet the 16'-0" requirement fo review note #25 for residential requirements.
|
FIR08-00801
| INSP-Final Inspection | 2/26/2009 | 2/26/2009 | 2/26/2009 3:33:59 PM | P | PASS |
|
|
permit finaled
|
FIR09-00142
| INSP-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 3:20:07 PM | A | PASS |
|
|
permit finaled
|
BLD08-01097
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 3:18:00 PM | A | FAIL |
|
|
No inspection performed since the city approved plans were not on site.
|
BLD08-01078
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 11:23:13 AM | A | FAIL |
|
|
Provide building address, repair the exit discharge light at the southeast corner and either provide correctly installed and functional duct smoke detectors or remove them.
|
BLD08-01783
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 10:26:42 AM | A | PASS |
|
|
Fire life safety passed
|
BLD05-03074
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 10:25:19 AM | A | FAIL |
|
|
Provide exit signs and emergency lighting as per the approved plans. Replace the round door knobs as marked on the plans with approved single action hardware.
|
BLD08-02487
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 9:46:12 AM | A | PASS |
|
|
life safety passed
|
FIR07-00932
| INSP-Final Inspection | 2/26/2009 | 2/26/2009 | 2/26/2009 8:00:29 AM | P | PASS |
|
|
permit finaled
|
BLD06-01451
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 7:59:18 AM | A | PART |
|
|
A temporary occupancy was given until the project related fire alarm permit is finaled. Life safety items will be ok to pass at that time.
|
BLD06-01450
| FIRE-Final Inspection | 2/25/2009 | 2/26/2009 | 2/26/2009 7:58:37 AM | A | PART |
|
|
A temporary occupancy was given until the project related fire alarm permit is finaled. Life safety items will be ok to pass at that time.
|