Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00158 Final2/26/20152/26/20152/26/2015 2:13:51 PMPFAIL
All the corrections have been completed and is ready for a final insp, any questions please let me know, thx, TW.
the ACCESS CODE is 4077 Phone #: ###-#### Inspection requested via web by Stephen Kren

Talked to worker on site
300.4 A NM through bored hole shall be protected when edge of hole is less than 1 1/4 inch from framing member edge
300.4 D NM shall be secured so outer edge of cable is not less than 1 1/4 inch from framing member edge
334.30 NM shall be secured within 12 inches of box.
ELE15-00158 Permanent Service2/26/20152/26/20152/26/2015 2:12:08 PMPPASS
All the corrections have been completed and is ready for a final insp, any questions please let me know, thx, TW.
the ACCESS CODE is 4077 Phone #: ###-#### Inspection requested
via web by Stephen Kren

P/S, O/H, R/C, OK
ELE15-00450 Temporary Service2/25/20152/26/20152/26/2015 1:38:48 PMPPART
Brian Phone #: ###-####
Power to two temporary job trailers, 100 amp each
ELE11-00368 Final2/26/20152/26/20152/26/2015 12:45:36 PMPPASS
New permit on project. X-Ref to permit ELE14-01652
ELE11-00368 ELE-Aging Inspection2/26/20152/26/20152/26/2015 12:44:55 PM DONE
see Final
ELE14-03372 Final2/26/20152/26/20152/26/2015 12:34:33 PMPFAIL
Larry-call for access Phone #: ###-####
210.12 Arc fault protection required in bedroom outlets, new smoke detectors
BCC 4.05.26 Trim out inspection, all items required to be functional. smokes
ELE13-00426 ELE-Aging Inspection2/26/20152/26/20152/26/2015 10:09:28 AM DONE
under construction
ELE15-00500 Final2/26/20152/26/20152/26/2015 9:32:57 AMPPASS
Phone #: ###-#### Inspection requested via web by Andy Derrick
Final OK
ELE15-00500 Electrical Rough-In2/25/20152/26/20152/26/2015 9:32:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Andy Derrick
RI and Final
ELE15-00198 Final2/25/20152/26/20152/26/2015 9:01:19 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson
corrections made, final oK
ELE15-00346 Electrical Rough-In2/26/20152/26/20152/26/2015 8:47:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by kendall bender
Called Mike
250.148 (C) Metal Boxes. A connection shall be made between the
one or more equipment grounding conductors and a metal
box by means of a grounding screw that shall be used for
no other purpose, equipment listed for grounding, or a
listed grounding device.
300.4(A) Cables and Raceways Through Wood Members.
(1) Bored Holes. In both exposed and concealed locations,
where a cable- or raceway-type wiring method is installed
through bored holes in joists, rafters, or wood members,
holes shall be bored so that the edge of the hole is not less
than 32 mm (11/4 in.) from the nearest edge of the wood
member. Where this distance cannot be maintained, the
cable or raceway shall be protected from penetration by
screws or nails by a steel plate(s) or bushing(s), at least
1.6 mm (1/16 in.) thick, and of appropriate length and width
installed to cover the area of the wiring.
314.29 Boxes, Conduit Bodies, and Handhole Enclosures
to Be Accessible. Boxes, conduit bodies, and handhole
enclosures shall be installed so that the wiring contained
in them can be rendered accessible without removing
any part of the building or structure or, in underground circuits,
without excavating sidewalks, paving, earth, or other
substance that is to be used to establish the finished grade.