ELE15-00158
| Final | 2/26/2015 | 2/26/2015 | 2/26/2015 2:13:51 PM | P | FAIL |
|
|
All the corrections have been completed and is ready for a final insp, any questions please let me know, thx, TW. the ACCESS CODE is 4077 Phone #: ###-#### Inspection requested via web by Stephen Kren
Talked to worker on site 300.4 A NM through bored hole shall be protected when edge of hole is less than 1 1/4 inch from framing member edge 300.4 D NM shall be secured so outer edge of cable is not less than 1 1/4 inch from framing member edge 334.30 NM shall be secured within 12 inches of box.
|
ELE15-00158
| Permanent Service | 2/26/2015 | 2/26/2015 | 2/26/2015 2:12:08 PM | P | PASS |
|
|
All the corrections have been completed and is ready for a final insp, any questions please let me know, thx, TW. the ACCESS CODE is 4077 Phone #: ###-#### Inspection requested via web by Stephen Kren
P/S, O/H, R/C, OK
|
ELE15-00450
| Temporary Service | 2/25/2015 | 2/26/2015 | 2/26/2015 1:38:48 PM | P | PART |
|
|
Brian Phone #: ###-#### Power to two temporary job trailers, 100 amp each
|
ELE11-00368
| Final | 2/26/2015 | 2/26/2015 | 2/26/2015 12:45:36 PM | P | PASS |
|
|
New permit on project. X-Ref to permit ELE14-01652
|
ELE11-00368
| ELE-Aging Inspection | 2/26/2015 | 2/26/2015 | 2/26/2015 12:44:55 PM | | DONE |
|
|
see Final
|
ELE14-03372
| Final | 2/26/2015 | 2/26/2015 | 2/26/2015 12:34:33 PM | P | FAIL |
|
|
Larry-call for access Phone #: ###-#### 210.12 Arc fault protection required in bedroom outlets, new smoke detectors BCC 4.05.26 Trim out inspection, all items required to be functional. smokes
|
ELE13-00426
| ELE-Aging Inspection | 2/26/2015 | 2/26/2015 | 2/26/2015 10:09:28 AM | | DONE |
|
|
under construction
|
ELE15-00500
| Final | 2/26/2015 | 2/26/2015 | 2/26/2015 9:32:57 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Andy Derrick Final OK
|
ELE15-00500
| Electrical Rough-In | 2/25/2015 | 2/26/2015 | 2/26/2015 9:32:52 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Andy Derrick RI and Final
|
ELE15-00198
| Final | 2/25/2015 | 2/26/2015 | 2/26/2015 9:01:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson corrections made, final oK
|
ELE15-00346
| Electrical Rough-In | 2/26/2015 | 2/26/2015 | 2/26/2015 8:47:07 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Called Mike 250.148 (C) Metal Boxes. A connection shall be made between the one or more equipment grounding conductors and a metal box by means of a grounding screw that shall be used for no other purpose, equipment listed for grounding, or a listed grounding device. 300.4(A) Cables and Raceways Through Wood Members. (1) Bored Holes. In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 32 mm (11/4 in.) from the nearest edge of the wood member. Where this distance cannot be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate(s) or bushing(s), at least 1.6 mm (1/16 in.) thick, and of appropriate length and width installed to cover the area of the wiring. 314.29 Boxes, Conduit Bodies, and Handhole Enclosures to Be Accessible. Boxes, conduit bodies, and handhole enclosures shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building or structure or, in underground circuits, without excavating sidewalks, paving, earth, or other substance that is to be used to establish the finished grade.
|