Inspections for the day of: Friday, February 26, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00537 Permanent Service2/26/20162/26/20162/26/2016 3:10:36 PMPPASS
David p/s o/h rec ok
ELE16-00240 Final2/26/20162/26/20162/26/2016 2:49:11 PMPPASS
Ken Phone #: ###-#### disconnect and ul listed final ok
ELE16-00240 Electrical Rough-In2/26/20162/26/20162/26/2016 2:48:29 PMPPASS
Ken Phone #: ###-#### R/I OK
ELE15-03849 Rough-In Permanent Service2/26/20162/26/20162/26/2016 2:38:54 PMPPASS
Underground Phone #: ###-#### Inspection requested via web by Stan Woodward remainder of exterior underground raceways r/i ok 100% NOTE:NO P/S NEEDED ALREADY RECEIVED YESTERDAY
ELE15-04089 Electrical Rough-In2/25/20162/26/20162/26/2016 2:14:49 PMPPASS
underground rough-in Phone #: ###-#### Inspection requested via web by Tom Betty r/i underslab raceways 100% , including slurried fire pump conduits and electrical room conduits
ELE15-01348 Electrical Rough-In2/26/20162/26/20162/26/2016 1:56:25 PMPPASS
Wayne Phone #: ###-#### r/i walls division 2 and 3 walls and bathrooms see blue highlighted area on Wayne's plans
ELE16-00478 Final2/26/20162/26/20162/26/2016 1:08:34 PMPPASS
Greg is the contact his cell no. is
###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates final ok
ELE16-00506 Electrical Rough-In2/26/20162/26/20162/26/2016 12:58:46 PMPPASS
We are requesting a inspection of the crane we just hooked up. Our contact is Tony @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate r/i u.ground, disconnect concrete encased electrode and feeder to crane ok
ELE15-02825 Final2/25/20162/26/20162/26/2016 10:42:25 AMANR
Semir Phone #: ###-#### Both GFCI receptacles also need to be tamper resistant
ELE16-00165 Final2/25/20162/26/20162/26/2016 9:48:30 AMAFAIL
Call Scott 30 min prior ###-#### Phone #: ###-#### Inspection requested via web by danny perrine 110.16-electrical equipment such as panels that are in "other than dwellings" shall be marked "arc flash warning" to warn of potential arc flash. 210.8(B)(5)- GFCI protection required for receptacles within 6 foot of sinks such as (janitors closets)
ELE16-00518 Final2/26/20162/26/20162/26/2016 9:23:46 AMAPASS
New Air conditioner wired. Phone #: ###-#### Inspection requested via web by Greg Idsinga final ok greg said cutler hammer breaker listed to be in Sq D loadcenter
ELE16-00518 Electrical Rough-In2/26/20162/26/20162/26/2016 9:22:47 AMPPASS
New Air conditioner wired. Phone #: ###-#### Inspection requested via web by Greg Idsinga r/i ok
ELE16-00540 Electrical Rough-In2/25/20162/26/20162/26/2016 8:30:41 AMAPASS
Butch Phone #: ###-#### walls ok
ELE16-00566 Final2/25/20162/26/20162/26/2016 8:10:58 AMACANC
Phone #: ###-#### Inspection requested via web by Kelly Felin needed t/s
ELE16-00566 Temporary Service2/26/20162/26/20162/26/2016 8:10:26 AMPPASS
Phone #: ###-#### Inspection requested via web by Kelly Felin t/s o/h n ok