ELE03-02084
| Final | 2/26/2016 | 2/26/2016 | 2/26/2016 3:22:20 PM | P | PASS |
|
|
job complete, final ok
|
MIS16-00018
| ELE-Final | 2/26/2016 | 2/26/2016 | 2/26/2016 3:21:39 PM | P | PASS |
|
|
corrections completed, final ok
|
ELE15-03996
| Electrical Rough-In | 2/25/2016 | 2/26/2016 | 2/26/2016 3:12:45 PM | A | PASS |
|
|
Duct Bank Inspection on SW Corner of Building 50. Contact Pierre Elskamp. Phone #: ###-#### Inspection requested via web by Cathy Duchek Rough-in ok to pour first 30 ft. from SW corner of building 50
|
ELE16-00095
| Electrical Rough-In | 2/26/2016 | 2/26/2016 | 2/26/2016 10:47:49 AM | A | PASS |
|
|
Floor heat code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon rough-in ok cover CSA listed floorheat in master bath
|
ELE15-03436
| Final | 2/25/2016 | 2/26/2016 | 2/26/2016 9:56:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 2012 energy code requires at least 50 % energy savings lamps throughout inside of structure. Washer receptacle within 6ft of a sink reqires GFCI protection. A/C conductors are #12 THHN on a 30 amp branch circuit. No service receptacle within 25 ft. of A/C unit. Island GFCI receptacle will not reset after test. Panel cover screws missing.
|