Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-02084 Final2/26/20162/26/20162/26/2016 3:22:20 PMPPASS
job complete, final ok
MIS16-00018 ELE-Final2/26/20162/26/20162/26/2016 3:21:39 PMPPASS
corrections completed, final ok
ELE15-03996 Electrical Rough-In2/25/20162/26/20162/26/2016 3:12:45 PMAPASS
Duct Bank Inspection on SW Corner of Building 50. Contact Pierre Elskamp. Phone #: ###-#### Inspection requested via web by Cathy Duchek Rough-in ok to pour first 30 ft. from SW corner of building 50
ELE16-00095 Electrical Rough-In2/26/20162/26/20162/26/2016 10:47:49 AMAPASS
Floor heat code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon rough-in ok cover CSA listed floorheat in master bath
ELE15-03436 Final2/25/20162/26/20162/26/2016 9:56:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Brandon Hillman 2012 energy code requires at least 50 % energy savings lamps throughout inside of structure. Washer receptacle within 6ft of a sink reqires GFCI protection. A/C conductors are #12 THHN on a 30 amp branch circuit. No service receptacle within 25 ft. of A/C unit. Island GFCI receptacle will not reset after test. Panel cover screws missing.