Inspections for the day of: Tuesday, February 26, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS19-00054 ELE-Conference2/26/20192/26/20192/26/2019 2:10:14 PMPFAIL
Any questions call Jim Sly
No access. Told by individual on site new wiring to micro and dishwasher at least. No permit yet.
ELE19-00684 Final2/26/20192/26/20192/26/2019 1:46:49 PMPPASS
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
ELE19-00695 Electrical Rough-In2/26/20192/26/20192/26/2019 1:16:49 PMPPASS
wall rough-in for the bathroom Phone #: ###-#### Inspection requested via web by Winters LLC
Back bathroom wall rough in ok cover
ELE16-00386 ELE-Aging Inspection2/26/20192/26/20192/26/2019 1:15:57 PM PASS
Sent contractor text
ELE19-00090 Final2/25/20192/26/20192/26/2019 11:13:16 AMAFAIL
Please give me 30 minutes notice to get there and open up the house. Phone #: ###-#### Inspection requested via web by Dan Hilke
210.12- All outlets located in bedroom areas shall have AFCI protection, device shall be located where circuit receives its source.
250.140- Range and dryer circuits shall be 4-wire. Frames of appliance shall have bond with seperate equipment grounds.
314.25- All boxes shall have covers. Receptacles, switches, lights hanging on wires.
406.12- All 120 volt 15 and 20 amp receptacles shall be tamper resistant type.
408.4- Circuit directory shall be complete.
422.31- Appliances shall have a disconnecting means. DW, WH. 110.25 lockouts acceptable. * Explained only licensed wireman employed by him are allowed to perform work.
* No smoke detectors installed.
* To remove receptacle from west soffit and cord that is attached that runs to back of garage.
ELE18-04311 Final2/25/20192/26/20192/26/2019 10:43:31 AMAPASS
getting final for this site LED exterior, highbays, and tubes. Phone #: ###-#### Inspection requested via web by Tim Dunlop Final ok
ELE19-00683 Electrical Rough-In2/25/20192/26/20192/26/2019 9:52:39 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric
210.52(A)- Required receptacle outlet located in family room under window does not have wiring installed.
250.68(A)- Connection to gounding electrode system shall be sccessible. Mudring missing.
408.3(A)(2)- Barriers shall be in place to prevent accidental contact at line side terminals of panel.
* Please make sure all types of inspections needed are included in request. Permanent service appears ready but not included in request