MIS19-00054
| ELE-Conference | 2/26/2019 | 2/26/2019 | 2/26/2019 2:10:14 PM | P | FAIL |
|
|
Any questions call Jim Sly No access. Told by individual on site new wiring to micro and dishwasher at least. No permit yet.
|
ELE19-00684
| Final | 2/26/2019 | 2/26/2019 | 2/26/2019 1:46:49 PM | P | PASS |
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
ELE19-00695
| Electrical Rough-In | 2/26/2019 | 2/26/2019 | 2/26/2019 1:16:49 PM | P | PASS |
|
|
wall rough-in for the bathroom Phone #: ###-#### Inspection requested via web by Winters LLC Back bathroom wall rough in ok cover
|
ELE16-00386
| ELE-Aging Inspection | 2/26/2019 | 2/26/2019 | 2/26/2019 1:15:57 PM | | PASS |
|
|
Sent contractor text
|
ELE19-00090
| Final | 2/25/2019 | 2/26/2019 | 2/26/2019 11:13:16 AM | A | FAIL |
|
|
Please give me 30 minutes notice to get there and open up the house. Phone #: ###-#### Inspection requested via web by Dan Hilke 210.12- All outlets located in bedroom areas shall have AFCI protection, device shall be located where circuit receives its source. 250.140- Range and dryer circuits shall be 4-wire. Frames of appliance shall have bond with seperate equipment grounds. 314.25- All boxes shall have covers. Receptacles, switches, lights hanging on wires. 406.12- All 120 volt 15 and 20 amp receptacles shall be tamper resistant type. 408.4- Circuit directory shall be complete. 422.31- Appliances shall have a disconnecting means. DW, WH. 110.25 lockouts acceptable. * Explained only licensed wireman employed by him are allowed to perform work. * No smoke detectors installed. * To remove receptacle from west soffit and cord that is attached that runs to back of garage.
|
ELE18-04311
| Final | 2/25/2019 | 2/26/2019 | 2/26/2019 10:43:31 AM | A | PASS |
|
|
getting final for this site LED exterior, highbays, and tubes. Phone #: ###-#### Inspection requested via web by Tim Dunlop Final ok
|
ELE19-00683
| Electrical Rough-In | 2/25/2019 | 2/26/2019 | 2/26/2019 9:52:39 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric 210.52(A)- Required receptacle outlet located in family room under window does not have wiring installed. 250.68(A)- Connection to gounding electrode system shall be sccessible. Mudring missing. 408.3(A)(2)- Barriers shall be in place to prevent accidental contact at line side terminals of panel. * Please make sure all types of inspections needed are included in request. Permanent service appears ready but not included in request
|