MEC19-00792
| Final | 2/26/2019 | 2/26/2019 | 2/26/2019 3:51:44 PM | P | PASS |
|
|
Susan Phone #: ###-#### - furnace ac coil co ok
|
MIS19-00054
| MEC-Conference | 2/26/2019 | 2/26/2019 | 2/26/2019 3:12:06 PM | P | DONE |
|
|
Any questions call Jim Sly - no access to home - any mechanical working being performed needs a permit
|
MEC19-00632
| Final | 2/22/2019 | 2/26/2019 | 2/26/2019 3:11:00 PM | P | FAIL |
|
|
Please inspect after 1:30 PM. Barbara Martin ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - condensate line for unit above tv needs to be ran in 3/4 pvc - west side outdoor unit needs line set penetration sealed
|
MEC19-00823
| Final | 2/26/2019 | 2/26/2019 | 2/26/2019 2:56:07 PM | P | FAIL |
|
|
Please call Joey with any questions. Phone #: ###-#### Inspection requested via web by Joey Hickman - need to secure registers to ceiling grid
|
MEC19-00812
| Final | 2/25/2019 | 2/26/2019 | 2/26/2019 2:32:25 PM | P | NR |
|
|
Please call on way: Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - not ready still working on one unit heater's flue - need to see insulation sheilds installed
|
MEC19-00812
| Pressure Test | 2/25/2019 | 2/26/2019 | 2/26/2019 2:31:35 PM | P | PASS |
|
|
Please call on way: Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - 20lb gas pressure test ok for two new unit heaters - tagged meter location
|
MEC19-00819
| Pressure Test | 2/25/2019 | 2/26/2019 | 2/26/2019 1:30:23 PM | P | FAIL |
|
|
RICK IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER - gas piping installed doesnt match the approved drawings. The approved drawings show a new meter location on the north west side of new buidling. The gas piping that is installed looks like it will be installed on a existing gas line. this needs to be reviewed by the engineer and then approved by the city.
|
MEC19-00811
| Rough-in | 2/25/2019 | 2/26/2019 | 2/26/2019 12:03:35 PM | A | FAIL |
|
|
sealer inspection - call brandon @ ###-#### Phone #: ###-#### Inspection requested via web by Brandon Sorensen - duct seal ok - inspection failed because there is non rated materials in return plenum( roof drains) and if any data cables or t stat wiring to be installed need to be approve materials
|
MEC19-00561
| Final | 2/22/2019 | 2/26/2019 | 2/26/2019 11:37:39 AM | A | FAIL |
|
|
Please call when on your way Phone #: ###-#### Inspection requested via web by Andrea Grigsby - need to pull plumbing permit for water heater - furnace ac coil co ok
|
MEC19-00302
| Final | 2/25/2019 | 2/26/2019 | 2/26/2019 10:20:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone - final ok
|
MEC19-00302
| Pressure Test | 2/25/2019 | 2/26/2019 | 2/26/2019 10:19:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone - 5lb flue pressure test ok
|
MEC19-00820
| Rough-in | 2/25/2019 | 2/26/2019 | 2/26/2019 9:29:12 AM | A | PASS |
|
|
Please call Aaron with any questions. Thanks! Phone #: ###-#### Inspection requested via web by Aaron Shay - mini split R/I ok
|
MEC18-02359
| Mec-Aging Inspection | 2/26/2019 | 2/26/2019 | 2/26/2019 9:05:00 AM | | DONE |
|
|
talked with Steve at diamond heating and he said that the owner decided to not have the work performed. Steve is going to call the permits desk and void the permit/get a refund
|
MEC19-00437
| Final | 2/25/2019 | 2/26/2019 | 2/26/2019 9:01:58 AM | A | PASS |
|
|
Call ahead to meet // Lou Phone #: ###-#### - final ok
|
MEC19-00488
| Final | 2/25/2019 | 2/26/2019 | 2/26/2019 8:28:42 AM | A | PASS |
|
|
We had a partial pass pending electrical permit. The electrical permit has passed. Please pass mechanical final. Phone #: ###-#### Inspection requested via web by Arielle Hendricks - electrical permit was pulled final ok
|
MEC18-02343
| Mec-Aging Inspection | 2/26/2019 | 2/26/2019 | 2/26/2019 8:26:19 AM | | DONE |
|
|
Called Ashley Heating & Air and left Matt a voice mail about mechanical aging permit.
|