Inspections for the day of: Tuesday, February 27, 2001.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD00-02926 FIRE-Final Inspection2/26/20012/27/20012/27/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 02/26/2001 at 09:36:35. Contact: ###-####. need to test the alarms and sprinklers 2/27/2001 2:14:50 PM
FIR00-00289 INSP-Sprinkler Rough-in2/23/20012/27/20012/27/2001 12:00:00 AMAPART
9 am ###-#### fire pump test with reps from BC, CM, TVFP and UW. The suction pressure remained positive and all indications from pressure readings are the pump passed and will meet the system demand. 2/27/2001 10:44:14 AM
BLD00-01146 FIRE-Final Inspection2/26/20012/27/20012/27/2001 12:00:00 AMPPASS
fire fn - troy ###-####
FIR01-00036 INSP-Sprinkler Rough-in/Hydro2/26/20012/27/20012/27/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 02/26/2001 at 16:17:37. Contact: ###-####. okay to cover 2/27/2001 2:59:53 PM
BLD00-03531 FIRE-Conference2/27/20012/27/20012/27/2001 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 02/27/2001 at 10:41:29. Contact: ###-####. discussed requirements for using firemaster listing; AHU shutdown detectors; exit signs and extinguishers 2/27/2001 3:54:54 PM
BLD00-01720 FIRE-Sprinkler Rough-in2/27/20012/27/20012/27/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 2/27/2001 2:59:33 PM okay to cover