Inspections for the day of: Wednesday, February 27, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00294 FIRE-Final Inspection2/26/20022/27/20022/27/2002 12:00:00 AMACANC
no fire life/safety or sprinkler to sign off per the computer 2/27/2002 10:55:52 AM
FIR02-00023 INSP-Supply line flush2/26/20022/27/20022/27/2002 12:00:00 AMAPASS
Fire sprinkler system finaled 2/27/2002 4:35:44 PM
FIR02-00030 INSP-Sprinkler Rough-in2/26/20022/27/20022/27/2002 12:00:00 AMAPASS
OK for cover 2/27/2002 10:50:57 AM
FIR02-00030 INSP-Sprinkler Rough-in/Hydro2/26/20022/27/20022/27/2002 12:00:00 AMACANC
duplicate inspection 2/27/2002 10:51:23 AM
BLD01-01926 FIRE-Alarm Testing2/25/20022/27/20022/27/2002 12:00:00 AMPPART
Hood in the A&W section operated correctly but is missing the hood balance report. The KFC hood was not entirely piped but did shut down power and gas. It is missing the air balance reports as well. No alarms were tested. There are live exposed wiring in the valve box of the KFC hood. Contractor to install signs to designate manual pull stations 2/27/2002 2:29:56 PM
FIR01-00295 INSP-Sprinkler Rough-in/Hydro2/26/20022/27/20022/27/2002 12:00:00 AMPPART
Underground hydro OK. Above ground hydro failed 2/27/2002 3:13:19 PM
FIR01-00604 INSP-Final Inspection2/27/20022/27/20022/27/2002 12:00:00 AMPFAIL
70db minimum sound level in the upstairs bedroom is not met, remove alarm bell disconnect switch 2/27/2002 1:08:37 PM
BLD01-02628 FIRE-Final Inspection2/27/20022/27/20022/27/2002 12:00:00 AMPPASS
fire life/safety finaled 2/27/2002 11:10:45 AM
FIR02-00030 INSP-Sprinkler Rough-in/Hydro2/26/20022/27/20022/26/2002 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 02/26/2002 at 16:11:43. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 02/26/2002 at 16:17:12.