FIR39-00016
| FIR-Aging Inspection | 2/27/2003 | 2/27/2003 | 2/27/2003 12:00:00 AM | | CANC |
|
|
|
BLD02-00466
| FIRE-Final Inspection | 2/26/2003 | 2/27/2003 | 2/27/2003 12:00:00 AM | A | NR |
|
|
###-#### rescheduled for 2/28 as fire lane marking not ready 2/27/2003 12:25:15 PM
|
FIR02-00338
| INSP-Final Inspection | 2/27/2003 | 2/27/2003 | 2/27/2003 12:00:00 AM | P | PASS |
|
|
|
BLD01-03095
| FIRE-Final Inspection | 2/27/2003 | 2/27/2003 | 2/27/2003 12:00:00 AM | P | FAIL |
|
|
need strobe replaced in room 2 restroom; need remote reset switches for detectors on northside; need 2 hr test paperwork for generator; need to test transfer switch for main power to generator; remove exit sign by FACP; need zones at FACP 2/27/2003 4:52:09 PM
|
FIR02-00422
| INSP-Alarm Testing | 2/26/2003 | 2/27/2003 | 2/27/2003 12:00:00 AM | P | FAIL |
|
|
Grants #; Phone #: ###-#### Internet Inspection Request from: Terry Owsley replace non-working strobe in room 2 restroom; put zones on FACP; need remote LED's with reset for detectors on northside 2/27/2003 4:48:44 PM
|
FIR02-00422
| INSP-Final Inspection | 2/26/2003 | 2/27/2003 | 2/27/2003 12:00:00 AM | P | FAIL |
|
|
Grants #; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Grants #; Phone #: ###-#### Internet Inspection Request from: Terry Owsley replace non-working strobe in room 2 restroom; put zones on FACP; need remote LED's with reset for detectors on northside 2/27/2003 4:48:57 PM
|
BLD02-02675
| FIRE-Final Inspection | 2/26/2003 | 2/27/2003 | 2/26/2003 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|