FIR03-00734
| FIR-Aging Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | | FAIL |
|
|
I met with the restraunt owner and left his a notice to have the permit finaled by March 19, 2004 or I would need to red tag the appliances beneath the hood in question. 3/5/2004 12:51:58 PM
|
BLD03-02278
| FIRE-Final Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | A | PASS |
|
|
Life safety finaled
|
BLD03-02958
| FIRE-Final Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD03-03051
| FIRE-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with dave millers permission until the fire alarm system has been upgraded per the upgrade agreement dated 2/26/04 2/27/2004 9:13:53 AM
|
BLD03-01348
| FIRE-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/27/2004 8:17:48 AM
|
FIR03-00014
| INSP-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 2/27/2004 7:27:59 AM
|
BLD03-02235
| FIRE-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/27/2004 8:06:03 AM
|
FIR04-00128
| INSP-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
permit finaled. Hood system operated correctly 2/27/2004 4:04:15 PM
|
FIR04-00137
| INSP-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
permit finaled. Hood system operated correctly 2/27/2004 4:04:21 PM
|
FIR04-00030
| INSP-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | FAIL |
|
|
need to provide annual inspection for the fire sprinkler system. Provide ceiling tile at all sprinkler heads. Finish installing the correct sidewall heads beneath the overhead door. Sprinkler piping is ok to cover 2/27/2004 1:31:25 PM
|
BLD04-00066
| FIRE-Final Inspection | 2/26/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
fire alarm and fire life safety finaled 2/27/2004 11:58:04 AM
|
BLD04-00006
| FIRE-Final Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
fire alarm, fire sprinkler and fire life safety for the vanilla finish is finaled 2/27/2004 12:46:42 PM
|
FIR04-00087
| INSP-Final Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
FIR04-00100
| INSP-Final Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
FIR04-00035
| INSP-Sprinkler Rough-in/Hydro | 2/27/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | PASS |
|
|
demo finaled
|
FIR02-00022
| INSP-Final Inspection | 2/24/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | FAIL |
|
|
The in-duct smoke detectors did not operate. Verify a/v's operate. Provide city approved building plans for life safety review. 2/27/2004 3:34:30 PM
|
FIR02-00499
| INSP-Final Inspection | 2/24/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | FAIL |
|
|
The in-duct smoke detectors did not operate. Verify a/v's operate. Provide city approved building plans for life safety review. 2/27/2004 3:34:37 PM
|
FIR03-00224
| INSP-Final Inspection | 2/24/2004 | 2/27/2004 | 2/27/2004 12:00:00 AM | P | FAIL |
|
|
The in-duct smoke detectors did not operate. Verify a/v's operate. Provide city approved building plans for life safety review. 2/27/2004 3:34:45 PM
|