Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04644 Electrical Rough-In2/27/20062/27/20062/27/2006 4:16:00 PMPPASS
Ceiling inspection for 02/27/06 afternoon. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie
ELE05-03951 Final2/27/20062/27/20062/27/2006 4:00:44 PMPFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
only one circuit feeds kitchen counter
ELE06-00673 Temporary Service2/27/20062/27/20062/27/2006 3:43:32 PMPFAIL
Greg; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
install plastic romex connector on GEC
inuse cover on 240v recep is broken
install proper nipple to two gang weatherproof box.
ELE06-00687 Electrical Rough-In2/27/20062/27/20062/27/2006 2:53:33 PMPPASS
Bob -- call 1st before insp for key access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
access required to box in ceiling of large room in the basement
ELE05-04007 Conference2/27/20062/27/20062/27/2006 2:30:54 PMPCANC
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
reschedual for 8:30 am tomorrow.
ELE06-00690 Electrical Rough-In2/27/20062/27/20062/27/2006 2:10:57 PMPPASS
Todd -- for underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
underground to garage ok
ELE05-04586 Final2/27/20062/27/20062/27/2006 1:41:14 PMPPART
James; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
signed T/O Ok
still need show window outlets and isolate neutral in the disconnect by the service
ELE06-00121 Electrical Rough-In2/27/20062/27/20062/27/2006 1:07:23 PMPPART
###-#### rough on where we ran j boxes to tie in new service. carpenters want to cover wall. thanks pat; Phone #: ###-#### Internet Inspection Request from: joe wheeler
wall with stained window is ok but it requires an access panel for angle flex connectors.
ELE06-00677 Electrical Rough-In2/24/20062/27/20062/27/2006 10:29:44 AMAFAIL
###-####
this is a one room addition and requires some nail plates and explanation of why he is mixing #12 & #14 romex on the circuit.
I called and left a message.
ELE06-00635 Final2/22/20062/27/20062/27/2006 9:35:39 AMAFAIL
We upgraded the service to 200 amps, drove 2 ground rods,(waterpipe was plastic feeding house), replaced 2 existing garage fuse boxes with a new 200 amp panel and fed it with a 200 amp 4 wire circuit from the outside service.(#6020125isla). Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell

250.104 Bonding of Piping Systems and Exposed Structural Steel. (1) must go to the service.
(A) Metal Water Piping.

310.15 Ampacities for Conductors Rated 0-2000 Volts. Service conductors are only #2 al

250.140 Frames of Ranges and Clothes Dryers. the branch circuit originates at the service equipment.

314.28 Pull and Junction Boxes and Conduit Bodies. LB is listed for 3 3/0 only
ELE06-00678 Electrical Rough-In2/24/20062/27/20062/27/2006 8:30:10 AMANR
don ###-####
grounds not made up and not yet nailplated
ELE06-00578 Final2/24/20062/27/20062/27/2006 8:16:36 AMAPASS
steve; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa