ELE05-04644
| Electrical Rough-In | 2/27/2006 | 2/27/2006 | 2/27/2006 4:16:00 PM | P | PASS |
|
|
Ceiling inspection for 02/27/06 afternoon. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie
|
ELE05-03951
| Final | 2/27/2006 | 2/27/2006 | 2/27/2006 4:00:44 PM | P | FAIL |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong only one circuit feeds kitchen counter
|
ELE06-00673
| Temporary Service | 2/27/2006 | 2/27/2006 | 2/27/2006 3:43:32 PM | P | FAIL |
|
|
Greg; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong install plastic romex connector on GEC inuse cover on 240v recep is broken install proper nipple to two gang weatherproof box.
|
ELE06-00687
| Electrical Rough-In | 2/27/2006 | 2/27/2006 | 2/27/2006 2:53:33 PM | P | PASS |
|
|
Bob -- call 1st before insp for key access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong access required to box in ceiling of large room in the basement
|
ELE05-04007
| Conference | 2/27/2006 | 2/27/2006 | 2/27/2006 2:30:54 PM | P | CANC |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles reschedual for 8:30 am tomorrow.
|
ELE06-00690
| Electrical Rough-In | 2/27/2006 | 2/27/2006 | 2/27/2006 2:10:57 PM | P | PASS |
|
|
Todd -- for underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong underground to garage ok
|
ELE05-04586
| Final | 2/27/2006 | 2/27/2006 | 2/27/2006 1:41:14 PM | P | PART |
|
|
James; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong signed T/O Ok still need show window outlets and isolate neutral in the disconnect by the service
|
ELE06-00121
| Electrical Rough-In | 2/27/2006 | 2/27/2006 | 2/27/2006 1:07:23 PM | P | PART |
|
|
###-#### rough on where we ran j boxes to tie in new service. carpenters want to cover wall. thanks pat; Phone #: ###-#### Internet Inspection Request from: joe wheeler wall with stained window is ok but it requires an access panel for angle flex connectors.
|
ELE06-00677
| Electrical Rough-In | 2/24/2006 | 2/27/2006 | 2/27/2006 10:29:44 AM | A | FAIL |
|
|
###-#### this is a one room addition and requires some nail plates and explanation of why he is mixing #12 & #14 romex on the circuit. I called and left a message.
|
ELE06-00635
| Final | 2/22/2006 | 2/27/2006 | 2/27/2006 9:35:39 AM | A | FAIL |
|
|
We upgraded the service to 200 amps, drove 2 ground rods,(waterpipe was plastic feeding house), replaced 2 existing garage fuse boxes with a new 200 amp panel and fed it with a 200 amp 4 wire circuit from the outside service.(#6020125isla). Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
250.104 Bonding of Piping Systems and Exposed Structural Steel. (1) must go to the service. (A) Metal Water Piping.
310.15 Ampacities for Conductors Rated 0-2000 Volts. Service conductors are only #2 al
250.140 Frames of Ranges and Clothes Dryers. the branch circuit originates at the service equipment.
314.28 Pull and Junction Boxes and Conduit Bodies. LB is listed for 3 3/0 only
|
ELE06-00678
| Electrical Rough-In | 2/24/2006 | 2/27/2006 | 2/27/2006 8:30:10 AM | A | NR |
|
|
don ###-#### grounds not made up and not yet nailplated
|
ELE06-00578
| Final | 2/24/2006 | 2/27/2006 | 2/27/2006 8:16:36 AM | A | PASS |
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|