Inspections for the day of: Tuesday, February 27, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00658 INSP-Sprinkler Rough-in/Hydro2/27/20072/27/20072/27/2007 6:10:30 PMPNR
Inspection rescheduled per phone call with contractor.
FIR03-00673 INSP-Final Inspection2/26/20072/27/20072/27/2007 6:05:39 PMAPART
Need to verifiy items noted at last field inspection dated 1/12/04 per R. Jackson and inspect plan modification review details completed on 5/7/04.

FIR06-00531 FIR-Aging Inspection2/27/20072/27/20072/27/2007 5:55:50 PM DONE
wip
FIR06-01023 INSP-Sprinkler Rough-in/Hydro2/23/20072/27/20072/27/2007 5:54:20 PMPFAIL
Provide approved plans on site as required.
FIR07-00055 INSP-Sprinkler Rough-in/Hydro2/23/20072/27/20072/27/2007 5:53:33 PMPFAIL
Need approved plans on site to complete inspection.
FIR07-00054 INSP-Sprinkler Rough-in/Hydro2/23/20072/27/20072/27/2007 5:52:29 PMPFAIL
Missing approved plans on site.
FIR07-00053 INSP-Sprinkler Rough-in/Hydro2/23/20072/27/20072/27/2007 5:51:53 PMPFAIL
Approved plans must be on site.
FIR07-00051 INSP-Sprinkler Rough-in/Hydro2/23/20072/27/20072/27/2007 5:51:04 PMPFAIL
Need approved plans on site to complete inspection.
FIR06-00389 INSP-Final Inspection2/26/20072/27/20072/27/2007 12:55:39 PMAPASS
On site visit to verify clear panel. TI fire alarm permit finaled.
FIR06-00101 INSP-Sprinkler Rough-in/Hydro2/27/20072/27/20072/27/2007 12:44:50 PMPFAIL
Inspection for the antifreeze system hydrostatic test failed due to visual leakage at two locations, also the SW heads as installed under the exposed composite wood joist obstructed construction ceiling do not meet requirements of NFPA 13 8.4.2 (1).
BLD06-03172 FIRE-Final Inspection2/27/20072/27/20072/27/2007 12:34:30 PMPPASS
Life safety inspection passed, no signature card on site.
FIR05-00635 INSP-Final Inspection2/26/20072/27/20072/27/2007 11:16:23 AMAPASS
Per inspection completed 12/5/05, FA final inspection passed. Permit finaled.
FIR07-00100 INSP-Sprinkler Rough-in/Hydro2/26/20072/27/20072/27/2007 10:46:47 AMANR
Corrections are not yet complete for re-inspection.
FIR06-00897 INSP-Supply line flush2/26/20072/27/20072/27/2007 10:45:30 AMAPART
UG fire supply line flush completed okay.
FIR05-00758 INSP-Final Inspection2/26/20072/27/20072/27/2007 10:22:57 AMAPASS
Fire sprinkler permit finaled.
FIR05-00872 INSP-Final Inspection2/26/20072/27/20072/27/2007 10:22:10 AMAPASS
Fire sprinkler installation passed inspection.
FIR05-00455 INSP-Final Inspection2/26/20072/27/20072/27/2007 10:20:42 AMAPASS
Fire sprinkler work is acceptable, permit finaled.
FIR06-01009 INSP-Final Inspection2/26/20072/27/20072/27/2007 10:15:37 AMAPASS
Final fire alarm inspection passed.