Inspections for the day of: Wednesday, February 27, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02266 Final2/27/20082/27/20082/27/2008 4:03:58 PMPPASS
ok to final
ELE06-00408 Final2/27/20082/27/20082/27/2008 3:58:07 PMPFAIL
james Phone #: ###-#### called, left correction notice, NEC 408.4 shall provide circuit directory that is clear, concise, and explanatory for each circuit, 408.38 panelboard shall be dead-front, cover installed
ELE08-00389 Permanent Service2/27/20082/27/20082/27/2008 2:31:04 PMPPASS
brian Phone #: ###-#### p/s o/h rec ok
ELE08-00355 Final2/26/20082/27/20082/27/2008 1:40:22 PMPPASS
danny - please call ahead so i can meet you Phone #: ###-#### ok to final
ELE07-02179 Electrical Rough-In2/27/20082/27/20082/27/2008 12:46:34 PMPPASS
nathan Phone #: ###-#### corrections made, called,, ric ok
ELE07-04087 Final2/26/20082/27/20082/27/2008 10:55:31 AMAPASS
don Phone #: ###-#### corrections, ok to final
ELE07-03429 Electrical Rough-In2/26/20082/27/20082/27/2008 10:40:16 AMAFAIL
Jay Phone #: ###-#### or Travis at ###-#### called, left correction notice, NEC 334.30 nm cable shall be stapled within 12" of boxes, cabinets and every 4 1/2', 314.17(C) nm cable sheath shall extend minimum 1/4" inside box, and be secured within 8" of single gang boxes, 300.4(A)(1) edge of bored holes shall be 1 1/4" from face of framing members or protected by steel plate, 210.52(E) at least one receptacle shall be installed at front of dwelling and be accessible at grade level, BCC all make-up shall be done and boxes installed, tub is listed
ELE08-00349 Permanent Service2/26/20082/27/20082/27/2008 9:54:44 AMAPASS
Job site contact: Gene ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corrections made, p/s u/g n ok, 5 meters required
ELE08-00317 Final2/26/20082/27/20082/27/2008 9:12:29 AMAFAIL
DAVE CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy met contractor, left correction notice, BCC no violations shall be retained, NEC 300.11(A) raceways shall be secured in place, and not on grid, 330.30(B) mc cable shall be secured within 12" of box,358.30(A) emt shall be secured within 3' of box, 408.4 circuit directory shall be clear, concise, complete, and explanatory for each circuit, 725.3(B) abandoned class2,3, pltc cables shall be removed, 725.8 cass1,2,3 cables shall be installed in a workman like manner and be supported
ELE08-00415 Electrical Rough-In2/26/20082/27/20082/27/2008 8:33:36 AMAPASS
justin - kitchen area Phone #: ###-#### ric ok kitchen area
ELE08-00294 Final2/27/20082/27/20082/27/2008 8:12:53 AMAPASS
this to final the work I did another permit will be placed by someone else to finish the project Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to final, signed structural card