Inspections for the day of: Monday, February 27, 2012.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00938 ELE-Aging Inspection2/27/20122/27/20123/2/2012 1:28:15 PM DONE
still under construction, no calls for inspection
ELE11-00927 ELE-Aging Inspection2/27/20122/27/20122/29/2012 8:09:09 AM DONE
still under construction
ELE12-00371 Electrical Rough-In2/27/20122/27/20122/27/2012 2:43:09 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, told contractor shall staple nm cable, provide free conductor length, use nailplates, look at panel violations
ELE12-00390 Rough-In Permanent Service2/27/20122/27/20122/27/2012 2:04:54 PMPPASS
ryan Phone #: ###-#### ri ok except at j-box, p/s o/h rec ok
ELE12-00363 Permanent Service2/27/20122/27/20122/27/2012 1:35:00 PMPPASS
Eric Baker Phone #: ###-#### at final, check for water pipe ground and that riser strapped, p/s u/g rec ok
ELE11-02651 Final2/22/20122/27/20122/27/2012 12:49:17 PMAPASS
thank's 301 ok final
ELE12-00347 Electrical Rough-In2/24/20122/27/20122/27/2012 10:24:16 AMAPASS
Please call Harvey @ ###-#### 30 minutes before you will be there so he can unlock the building. Phone #: ###-#### >> Inspection requested via web by Celinda Winters ri ok
ELE12-00394 Rough-In Permanent Service2/26/20122/27/20122/27/2012 10:09:52 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.23 shall protect cables within 6' of attic access, 210.52 (H) shall provide receptacle in upper hall, BCC shall terminate nm cable in boxes in down bath
ELE12-00393 Temporary Service2/24/20122/27/20122/27/2012 9:27:25 AMAPASS
Temp Power Phone #: ###-#### >> Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE11-00557 Electrical Rough-In2/24/20122/27/20122/27/2012 8:54:47 AMAPASS
Job contact is Glen Corbeil ###-####. Rough-in inspection for East stairwell. Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok cover stairwell
ELE12-00365 Electrical Rough-In2/24/20122/27/20122/27/2012 8:29:05 AMAPASS
Phone #: ###-#### ri ok
ELE12-00345 Electrical Rough-In2/24/20122/27/20122/27/2012 8:10:19 AMAPASS
jamie Phone #: ###-#### u/g only ok cover