FIR13-00650
| INSP-Final Inspection | 2/26/2014 | 2/27/2014 | 2/27/2014 2:12:49 PM | A | PASS |
|
|
Permit finaled
|
FIR13-00403
| INSP-Final Inspection | 2/25/2014 | 2/27/2014 | 2/27/2014 2:09:23 PM | A | PASS |
|
|
Permit finaled
|
BLD13-02610
| FIRE-Final Inspection | 2/27/2014 | 2/27/2014 | 2/27/2014 1:08:01 PM | P | PASS |
|
|
Life safety passed
|
BLD14-00252
| FIRE-Final Inspection | 2/26/2014 | 2/27/2014 | 2/27/2014 12:55:56 PM | A | FAIL |
|
|
Repair the fire alarm system/provide verification that the system is monitored, install all ceiling tile, remove dead bolt at office, remove exit sign by fire sprinkler riser, provide fire extinguisher with current tag on the mezzanine, provide/repair all exit signs/emergency lights (see approved plans), provide racking permit or contact scott arellano with removal timeline.
|
FIR14-00092
| INSP-Sprinkler Rough-in/Hydro | 2/26/2014 | 2/27/2014 | 2/27/2014 8:36:52 AM | P | CANC |
|
|
Inspection must be done between 12 - 2 pm. Phone #: ###-#### >> Inspection requested via web by Mary Castle Inspection cancelled from web by: Mary Castle
|