ELE16-04017
| Electrical Rough-In | 2/27/2017 | 2/27/2017 | 2/27/2017 2:14:06 PM | P | PASS |
|
|
Underground branch rough-in for South Island and T1 branch conduits. Phone #: ###-#### Inspection requested via web by Debby Pierce Area noted rough in ok cover
|
ELE17-00037
| Final | 2/27/2017 | 2/27/2017 | 2/27/2017 1:38:08 PM | P | PART |
|
|
Final Inspection for Building #4 Contact Dan Hutchinson Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek 411, 413 not ready... rest TCO ok
|
ELE17-00491
| Temporary Service | 2/27/2017 | 2/27/2017 | 2/27/2017 1:05:33 PM | P | PASS |
|
|
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren 230.24(B)(4)- Overhead service entrance conductors shall have 18' clearence over alley. Pole set back 5' off alley, pole 14' tall. Angle of overhead conductors should be good when connected Idaho Power 25' pole straight across alley. t/s o/h n ok
|
ELE17-00489
| Rough-In Permanent Service | 2/24/2017 | 2/27/2017 | 2/27/2017 10:50:05 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE17-00095
| Temporary Service | 2/24/2017 | 2/27/2017 | 2/27/2017 9:45:55 AM | A | FAIL |
|
|
temp pole Phone #: ###-#### Inspection requested via web by Tracy Robertson 590.6(B)- All temp power shall have GFCI protection. 240 volt receptacle
|
ELE17-00093
| Temporary Service | 2/24/2017 | 2/27/2017 | 2/27/2017 9:20:31 AM | A | PASS |
|
|
temp pole Phone #: ###-#### Inspection requested via web by Tracy Robertson t/s u/g n ok
|