Inspections for the day of: Monday, February 27, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04017 Electrical Rough-In2/27/20172/27/20172/27/2017 2:14:06 PMPPASS
Underground branch rough-in for South Island and T1 branch conduits. Phone #: ###-#### Inspection requested via web by Debby Pierce
Area noted rough in ok cover
ELE17-00037 Final2/27/20172/27/20172/27/2017 1:38:08 PMPPART
Final Inspection for Building #4
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
411, 413 not ready... rest TCO ok
ELE17-00491 Temporary Service2/27/20172/27/20172/27/2017 1:05:33 PMPPASS
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
230.24(B)(4)- Overhead service entrance conductors shall have 18' clearence over alley. Pole set back 5' off alley, pole 14' tall. Angle of overhead conductors should be good when connected Idaho Power 25' pole straight across alley. t/s o/h n ok
ELE17-00489 Rough-In Permanent Service2/24/20172/27/20172/27/2017 10:50:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE17-00095 Temporary Service2/24/20172/27/20172/27/2017 9:45:55 AMAFAIL
temp pole Phone #: ###-#### Inspection requested via web by Tracy Robertson
590.6(B)- All temp power shall have GFCI protection. 240 volt receptacle
ELE17-00093 Temporary Service2/24/20172/27/20172/27/2017 9:20:31 AMAPASS
temp pole Phone #: ###-#### Inspection requested via web by Tracy Robertson
t/s u/g n ok