Inspections for the day of: Tuesday, February 27, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-02979 FIRE-Final Inspection2/27/20182/27/20182/27/2018 2:33:00 PMPFAIL
Need the project related fire sprinkler underground and overhead permits finaled. Need the project related fire alarm permit finaled. A stand alone smoke alarm is being required to be added in the Infant room as per the Assistant Fire Marshal. A separate permit is needed for the second business located in this building. Deadbolts need to be removed. Approved hardware is needed on the Restroom Barn Doors. Fire extinguishers need to be mounted. Exit signs and emergency lights need to be tested. Small documents need to be on site. An address needs to be installed as discussed.


Steve-please call 10 minutes prior to meet-wants to go threw inspection with him Phone #: ###-####
FIR17-00559 INSP-Final Inspection2/27/20182/27/20182/27/2018 2:28:30 PMPFAIL
Was unable to test the interconnection with the fire sprinkler system due to work being performed.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug
FIR18-00073 INSP-Final Inspection2/27/20182/27/20182/27/2018 2:27:38 PMPPASS
Hood suppression system functioned correctly

Dave Phone #: ###-####
FIR17-00607 INSP-Final Inspection2/27/20182/27/20182/27/2018 2:26:06 PMPFAIL
Need the head guards installed and the coverage modified under the exterior canopy and the interconnection with the fire alarm panel tested..


Call prior to going Phone #: 20887175 >> Inspection requested via mobile web by Mike
FIR17-00700 INSP-Sprinkler Rough-in2/26/20182/27/20182/27/2018 12:40:13 PMAFAIL
Todays inspection was for the second floor. I noted that the piping and pendant heads had not been installed where shown on the plans. This caused heads to be overspaced off walls, blocked by walls and located too close to each other in many locations. I also noted that the insulation needs to be "pocketed" around the piping to the dry sidewall heads in many locations and it also needs to be placed above the piping in several locations. I also noted a lack of coverage in the lobby area on the second floor and the first floor that Jim Danes is going to address. Also additional fittings have been added in to the gridded system that will need to be verified with hydraulic calculations to the plan reviewer.


2nd Floor Rough In Cover. Thank you! Phone #: ###-#### Inspection requested via web by Connie Danes
BLD17-04004 FIRE-Final Inspection2/26/20182/27/20182/27/2018 12:04:02 PMPFAIL
Life safety will be ok for sign off when an additional fire extinguisher is provided as discussed and the fire alarm permit is finaled

David Phone #: ###-####
FIR17-00758 INSP-Final Inspection2/27/20182/27/20182/27/2018 12:02:25 PMPFAIL
No city approved plans or small documents on site. I did witness the audio/visual devices function in the scope of work but someone has disabled the devices on the rest of the floor. These devices will need to be repaired and tested prior to a final sign off.
BLD18-00187 FIRE-Final Inspection2/22/20182/27/20182/27/2018 11:50:50 AMAPASS
life safety passed. Suite number to be posted prior to building inspection
FIR18-00102 INSP-Final Inspection2/23/20182/27/20182/27/2018 11:50:17 AMAPASS
Permit finaled
BLD18-00516 FIRE-Final Inspection2/26/20182/27/20182/27/2018 9:06:24 AMAPASS
Life safety passed. Matt is going to remove the two non-functional exit signs prior to a building inspection

Matt Phone #: ###-####
BLD17-04052 FIRE-Final Inspection2/26/20182/27/20182/27/2018 8:41:19 AMAPART
A temporary for life safety is being given until the permanant address is provided and the fire extinguisher is mounted with current tag as discussed.

Chris Phone #: ###-####
FIR18-00073 INSP-Sprinkler Rough-in/Hydro2/26/20182/27/20182/27/2018 12:00:00 AMPCANC
dave Phone #: ###-####

Wrong inspection type called in // C_P