Inspections for the day of: Wednesday, February 27, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00468 Permanent Service2/27/20192/27/20192/27/2019 2:22:11 PMPPASS
Phone #: ###-#### Inspection requested via web by Winters LLC
p/s o/h rec ok
ELE19-00477 Electrical Rough-In2/27/20192/27/20192/27/2019 1:52:17 PMPCANC
Call Luke to meet you there. ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
No repairs needed here, just service reconnect.
ELE19-00490 Electrical Rough-In2/27/20192/27/20192/27/2019 1:50:55 PMPPASS
Call Luke to meet you there. ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Only wiring damaged is located in "B" unit in bedroom closet. Replaced switch leg and water heater circuits. Rest of drywall removed to check wiring. No improvements made, if improvements are made rest will be required to be brought up to current code.
Unit "B" rough in ok cover
ELE19-00273 Electrical Rough-In2/26/20192/27/20192/27/2019 12:56:19 PMPPASS
Kitchen rewire insp Phone #: ###-#### Inspection requested via web by John VanZandt Kitchen rough in ok cover
ELE19-00240 Electrical Rough-In2/26/20192/27/20192/27/2019 11:25:52 AMAPASS
Garage rough Insp Phone #: ###-#### Inspection requested via web by John VanZandt
Panel hung and stuffed but grounding electrode not complete and feeders not done, No concrete encased electrode found.
Rest rough in ok cover
ELE18-04169 Final2/26/20192/27/20192/27/2019 10:55:36 AMAFAIL
*7285 Phone #: ###-#### Inspection requested via web by Ben Archibald
110.3- Furnace field connection if on interior of casing shall be in junction box provide as per manufacturers instructions. Interior wiring shall be 105 degree celcius rated.
314.16- Boses shall have adaquate free conductor space for all conductors and devices installed. Island receptacle boxes 8 cubic inch with 11.25 cubic inches of conductor installed.
356.30- LFNC shall be secured with in 12" of an enclosure. Strap AC whip.
ELE19-00683 Electrical Rough-In2/26/20192/27/20192/27/2019 9:41:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Icon Electric
Rough in ok cover
ELE19-00683 Permanent Service2/27/20192/27/20192/27/2019 9:41:28 AMPPASS
Phone #: ###-#### Inspection requested via web by Icon Electric
We will add inspection this one time. It is not our job to fix your missed requests.
p/s u/g n ok
ELE18-04855 Final2/26/20192/27/20192/27/2019 9:32:06 AMAPASS
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok