FIR18-00680
| INSP-Sprinkler Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 2:25:19 PM | P | FAIL |
|
|
Rough in passed with one exception on 2nd floor apt that Anthony will reseearch on possible obstruction. Tenting will need to be fixed in several areas lacking coverage. No piping to be covered,.
Call Anthony before heading out. Recheck based on Plan-Mod approval. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-04438
| FIRE-Conference | 2/27/2019 | 2/27/2019 | 2/27/2019 2:23:27 PM | P | DONE |
|
|
Met with Mike discussed requirements needed for final. Mike mentioned not having glycol system installed in time for final so we gave him Ron Johnson's phone and email to discuss possible TCO when they are ready.
Mike Phone #: ###-####
|
FIR19-00144
| INSP-Sprinkler Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 1:31:38 PM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
Rick Fry Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
NAF18-00124
| INSP-Sprinkler Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 10:30:25 AM | A | PASS |
|
|
First floor corridor piping east of column line 6 is ok for cover. One additional pendant may be required at the east stairwell/corridor alcove due to the corridor pendant head half spacing being exceeded. Call prior to going Phone #: 2082979090 >> Inspection requested via mobile web by Ken
|
NAF19-00013
| INSP-Final | 2/26/2019 | 2/27/2019 | 2/27/2019 10:16:25 AM | A | FAIL |
|
|
Provide 6" address numbers, remove deadbolt from the main exit, provide sticker at the main exit.
Call prior to going Phone #: 9723417105 >> Inspection requested via mobile web by Darcy
|
FIR18-00901
| INSP-Sprinkler Rough-in | 2/26/2019 | 2/27/2019 | 2/27/2019 9:35:36 AM | A | PASS |
|
|
Bury depth has been corrected. Underground supply piping is ok for cover.
Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD19-00180
| FIRE-Final Inspection | 2/26/2019 | 2/27/2019 | 2/27/2019 8:38:20 AM | A | PASS |
|
|
Life safety passed. Johnathan Phone #: ###-####
|
FIR18-00940
| INSP-Final Inspection | 2/26/2019 | 2/27/2019 | 2/27/2019 8:09:46 AM | A | PASS |
|
|
Permit finaled
Inspection has be around 7or 7:30am Phone #: ###-#### Inspection requested via web by Rafe Barrett
|
BLD18-03819
| FIRE-Final Inspection | 2/26/2019 | 2/27/2019 | 2/27/2019 8:09:24 AM | A | PASS |
|
|
life safety passed. Door mag fuctioned correctly. Call ahead // John Phone #: ###-####
|