Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04932 Final2/27/20202/27/20202/27/2020 2:37:59 PMPPASS
if locked code is 2019 Phone #: ###-#### Inspection requested via web by Chris Berthelot
Final ok
ELE19-04153 Final2/26/20202/27/20202/27/2020 2:00:19 PMPPASS
lock box is attached to gas meter code is 1897 Phone #: ###-#### Inspection requested via web by Ryan Wake
Final ok
ELE20-00687 Final2/27/20202/27/20202/27/2020 1:21:47 PMPCANC
Robert Phone #: ###-####
Scheduled wrong day
ELE20-00468 Electrical Rough-In2/26/20202/27/20202/27/2020 11:20:00 AMAPASS
Exterior lighting
Garage
Butlers pantry
Back patio ceiling heaters Phone #: ###-#### Inspection requested via web by Kurt Carlson
Soffits-patio-bulters pantry ok to cover
Also discussed service change options from 400amp to 600amp and location of disc above CT can not over 6'7" and will provide a platform for work spce clearences,grounding to be brought up or use existing once verifeid location and connection point.....
ELE20-00672 Temporary Service2/26/20202/27/20202/27/2020 10:00:12 AMAPASS
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
t/s u/g n ok
ELE20-00673 Temporary Service2/26/20202/27/20202/27/2020 9:59:50 AMAPASS
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
t/s u/g n ok
ELE20-00584 Rough-In Permanent Service2/26/20202/27/20202/27/2020 9:43:31 AMAPASS
Wire addition to garage and set new service to sub feed old location - energize service for relocation. Phone #: ###-#### Inspection requested via web by Kendra Lanham
Will need to verify sub-feed once service is disc....
Garage rough-in ok to ok cover
p/s o/h rec ok
New panel location is in a possible fire wall and EC will talk to GC about this location and may need to be moved or turned into a J-Box depending on BLD inspectors view....