Inspections for the day of: Friday, February 28, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00034 INSP-Final Inspection2/27/20032/28/20032/28/2003 12:00:00 AMAFAIL
The city approved sprinkler plans show a maximum spacing of 148 square feet in the conference room 009 and the lobby 002. The sprinkler pendants as installed exceed this. One sprinkler upright has a bent deflector and needs replacing 2/28/2003 3:02:02 PM
BLD02-02618 FIRE-Final Inspection2/27/20032/28/20032/28/2003 12:00:00 AMAFAIL
the tenant is storing broken fax and copy machines in the front area. the sprinkler pendants are over space for ordinary hazard occupancy. Sprinkler plans will need to be submitted 2/28/2003 2:02:03 PM
FIR03-00080 INSP-Sprinkler Rough-in/Hydro2/27/20032/28/20032/28/2003 12:00:00 AMAPASS
sprinklers are ok to cover 2/28/2003 12:27:37 PM
FIR03-00013 INSP-Final Inspection2/28/20032/28/20032/28/2003 12:00:00 AMPFAIL
nicole; Phone #: ###-#### The contractor still did not read all of the review notes and provide the required information even though some items have been corrected. No inspection was performed. A reinspection fee will be attached. 2/28/2003 3:05:11 PM
FIR01-00577 INSP-Final Inspection2/28/20032/28/20032/28/2003 12:00:00 AMPPASS
fire alarm finaled 2/28/2003 2:06:00 PM
FIR01-00543 INSP-Final Inspection2/28/20032/28/20032/28/2003 12:00:00 AMPPASS
fire sprinklers finaled
BLD01-01109 FIRE-Final Inspection2/28/20032/28/20032/28/2003 12:00:00 AMPPASS
Fire life safety, fire alarm and fire sprinklers finaled