Inspections for the day of: Wednesday, February 28, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00958 INSP-Sprinkler Rough-in/Hydro2/27/20072/28/20073/1/2007 11:53:49 AMAFAIL
Inspection was for a partial on the underground supply line and remote FDC. Both pipes from the stub out to roughly twenty feet were not at the required bury depth of 4'6". The only piping in the trench was the twenty feet. Also the new FDC location has not been approved yet
FIR06-00614 INSP-Final Inspection2/27/20072/28/20072/28/2007 4:44:18 PMPFAIL
Need to change the the description for the zones at the monitoring agency. Also need the sample tube installed in the duct smoke detector.
FIR07-00133 INSP-Final Inspection2/28/20072/28/20072/28/2007 3:52:50 PMPFAIL
Not all of the work is complete. Sprinkler rough-in is complete for the most part. Still missing the canopy over the sidewall heads on the driving range and the plywood soffit is not complete.
FIR06-00641 INSP-Sprinkler Rough-in/Hydro2/27/20072/28/20072/28/2007 3:47:35 PMPPASS
Above ground hydro test passed.
FIR06-00953 INSP-Sprinkler Rough-in2/28/20072/28/20072/28/2007 3:03:03 PMPPART
See the city approved plans for locations where the overhead sprinkler piping is ok to cover
FIR07-00111 INSP-Final Inspection2/28/20072/28/20072/28/2007 2:11:31 PMPPASS
Permit finaled
BLD06-01803 FIRE-Final Inspection2/27/20072/28/20072/28/2007 2:04:23 PMPFAIL
No inspection performed. Need fire alarm permit to be finaled first. The fire alarm permit failed today.
FIR06-00585 INSP-Alarm Testing2/27/20072/28/20072/28/2007 12:05:54 PMAFAIL
Provide a/v's in the two addtional rooms as marked on the plans that are being used as common areas and provide a horn as per plans in the corridor.
BLD06-02610 FIRE-Final Inspection2/28/20072/28/20072/28/2007 11:19:31 AMAPASS
life safety finaled
FIR06-00224 INSP-Final Inspection2/23/20072/28/20072/28/2007 10:53:32 AMPCANC
Contact is Brian at ###-####. Thank you! Phone #: ###-#### Inspection cancelled from web by: Stan Beus
BLD05-01452 FIRE-Final Inspection2/27/20072/28/20072/28/2007 10:48:26 AMAFAIL
John was not at the job site and could not get the fire alarm people here to test the two smoke detectors for door release while I was here. It will have to be rescheduled. Per Per what Ron Hill told John the entire second floor fire inspection is tied into this small remodel permit.
FIR06-00778 INSP-Sprinkler Rough-in2/27/20072/28/20072/28/2007 10:28:43 AMAPASS
Sprinkler piping is ok to cover
FIR06-00466 INSP-Alarm Testing2/26/20072/28/20072/28/2007 10:07:19 AMAFAIL
The only item tested was the first floor a/v's. Many are overspaced. Strobes are lacking in the corridors formed by the full height racks in the stockrooms. THe racks also form corridors without a/v's within 15' of the ends. Also noted some offices on the second floor that have well over one person in them and not a/v's. No sound levels have been verified yet or end of line voltage drops.
FIR06-00641 INSP-Sprinkler Rough-in/Hydro2/27/20072/28/20072/27/2007 4:55:00 PMACANC
Contact: Todd Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley