FIR06-00958
| INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 2/28/2007 | 3/1/2007 11:53:49 AM | A | FAIL |
|
|
Inspection was for a partial on the underground supply line and remote FDC. Both pipes from the stub out to roughly twenty feet were not at the required bury depth of 4'6". The only piping in the trench was the twenty feet. Also the new FDC location has not been approved yet
|
FIR06-00614
| INSP-Final Inspection | 2/27/2007 | 2/28/2007 | 2/28/2007 4:44:18 PM | P | FAIL |
|
|
Need to change the the description for the zones at the monitoring agency. Also need the sample tube installed in the duct smoke detector.
|
FIR07-00133
| INSP-Final Inspection | 2/28/2007 | 2/28/2007 | 2/28/2007 3:52:50 PM | P | FAIL |
|
|
Not all of the work is complete. Sprinkler rough-in is complete for the most part. Still missing the canopy over the sidewall heads on the driving range and the plywood soffit is not complete.
|
FIR06-00641
| INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 2/28/2007 | 2/28/2007 3:47:35 PM | P | PASS |
|
|
Above ground hydro test passed.
|
FIR06-00953
| INSP-Sprinkler Rough-in | 2/28/2007 | 2/28/2007 | 2/28/2007 3:03:03 PM | P | PART |
|
|
See the city approved plans for locations where the overhead sprinkler piping is ok to cover
|
FIR07-00111
| INSP-Final Inspection | 2/28/2007 | 2/28/2007 | 2/28/2007 2:11:31 PM | P | PASS |
|
|
Permit finaled
|
BLD06-01803
| FIRE-Final Inspection | 2/27/2007 | 2/28/2007 | 2/28/2007 2:04:23 PM | P | FAIL |
|
|
No inspection performed. Need fire alarm permit to be finaled first. The fire alarm permit failed today.
|
FIR06-00585
| INSP-Alarm Testing | 2/27/2007 | 2/28/2007 | 2/28/2007 12:05:54 PM | A | FAIL |
|
|
Provide a/v's in the two addtional rooms as marked on the plans that are being used as common areas and provide a horn as per plans in the corridor.
|
BLD06-02610
| FIRE-Final Inspection | 2/28/2007 | 2/28/2007 | 2/28/2007 11:19:31 AM | A | PASS |
|
|
life safety finaled
|
FIR06-00224
| INSP-Final Inspection | 2/23/2007 | 2/28/2007 | 2/28/2007 10:53:32 AM | P | CANC |
|
|
Contact is Brian at ###-####. Thank you! Phone #: ###-#### Inspection cancelled from web by: Stan Beus
|
BLD05-01452
| FIRE-Final Inspection | 2/27/2007 | 2/28/2007 | 2/28/2007 10:48:26 AM | A | FAIL |
|
|
John was not at the job site and could not get the fire alarm people here to test the two smoke detectors for door release while I was here. It will have to be rescheduled. Per Per what Ron Hill told John the entire second floor fire inspection is tied into this small remodel permit.
|
FIR06-00778
| INSP-Sprinkler Rough-in | 2/27/2007 | 2/28/2007 | 2/28/2007 10:28:43 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
FIR06-00466
| INSP-Alarm Testing | 2/26/2007 | 2/28/2007 | 2/28/2007 10:07:19 AM | A | FAIL |
|
|
The only item tested was the first floor a/v's. Many are overspaced. Strobes are lacking in the corridors formed by the full height racks in the stockrooms. THe racks also form corridors without a/v's within 15' of the ends. Also noted some offices on the second floor that have well over one person in them and not a/v's. No sound levels have been verified yet or end of line voltage drops.
|
FIR06-00641
| INSP-Sprinkler Rough-in/Hydro | 2/27/2007 | 2/28/2007 | 2/27/2007 4:55:00 PM | A | CANC |
|
|
Contact: Todd Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley
|